IMPORTANT SAFETY INFORMATION
!
WARNING! Not Following these instructions may cause severe injury or death.

Secondary Entrapment Protection Requirements

IMPORTANT: SECONDARY PROTECTION MUST BE INSTALLED
• REQUIRED BY UL 325, an approved MONITORED secondary entrapment
protection sensor is REQUIRED to be installed in all areas accessible to potential
entrapment and pinch points.
• The installed sensor MUST be "10K Resistor Based".
• At least ONE monitored sensor MUST be connected. (also, refer to page 43)
• You may connect up to FOUR monitored sensors, wired parallel.
• Failure to install an approved monitored secondary entrapment protection
sensor will render the gate operator INOPERABLE until one is installed.
• Consult the installation manual of the sensor for detailed information about the
usage, installation and maintenance.
• This type of installation will only reverse the gate approximately 12" in the opposite
direction it was traveling when the sensor is triggered. (also, refer to page 43)
• This type on installation is to protect against entrapment only and DOES NOT
reverse the gate all the way back to its limits when the sensor is triggered. (also,
refer to page 43)
• Use only UL Listed Edge Sensor and Photoelectric Beams.
Photo Beam (non-contact sensor)
Edge Sensor (contact sensor)
1 0