Output Function Menu Mode - Honeywell ADEMCO VISTA SERIES Programming Manual

Hide thumbs Also See for ADEMCO VISTA SERIES:
Table of Contents

Advertisement

XX OUTPUT TYPE
DELETE
0
"A"
XX UNIT No.
yy
"B"
XX MODULE ADDR
07-15
yy
XX REL POSITION
1-4
zz
∗ ∗ ∗ ∗ 80 OUTPUT FUNCTION MENU MODE
(press ∗ ∗ ∗ ∗ 80 while in Programming mode) The Output Definition Worksheet is on page 46.
Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output
devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified
by an output function number, and includes the following components:
Output Definition Components
Component
Description
Output Function No.
A reference number that defines an output's characteristics.
Activated By
Determines whether the initiating event occurs on a zone, a zone list, or a zone type.
Event
Event that triggers the output action. Can be an event occurring on a specific zone number or a zone list, or a
specific zone type.
Partition
If the output is activated by zone type, this defines the partition in which the programmed event is to cause the
device action.
Output Action
Defines the action of the relay/X-10 device when the defined event occurs. Can close for 2 seconds, stay
closed until reset, continuously pulse (1-second close-open-close-open, etc.), toggle the device state, or
activate for a defined duration (set in data field *177).
Output No.
Assigns this function to a specific output number (defined in *79 Menu Mode). This is the output number that will
perform this function upon the triggering event. Note that each defined function is associated with only one
output number. This means that if more than one output device needs to perform this particular function, you
need to define another output function number with the same attributes, but assign the appropriate output
number. (i.e. output devices can be assigned more than one function number, but each function number can
only be assigned a single output number.
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 (as
programmed in *79 Menu Mode), program the following in *80 Menu Mode:
Prompt
Output Funct. #
=
Activated By:
=
Enter Zn No.
=
Output Action
=
Output Number
=
Output Type
0 = delete
1 = relay on 4204/4229
2 = Powerline Carrier Device
[∗] to continue
Unit Number
01-16 = predefined address
[∗] to continue
Module Address
07-15 = predefined address
[∗] to continue
REMOTE SERVICES NOTE: If
using the communication device's
Multi-Mode 4204 or 2-4204
options, select one of the 4204
addresses, though a physical
4204 module is not installed. If
using 2-4204 multi-mode option,
the second 4204 address is
automatically one number higher
than the first address. Make sure
these addresses are not used by
physical 4204 modules that may
be installed. If using Multi-Mode
Enhanced Reports option, RIS
must be enabled in field *91;
when enabled, address 25 is
automatically assigned. See the
communication device's
instructions to enable Multi-Mode.
Relay Position
1-4 = relay position
[∗] to continue
Entry
01 (assuming this is the first output function)
3 (zone number)
04 (requires 2-digit zone numbers)
3 (continuous pulse)
02 (device mapped in *79 Menu Mode)
Select whether this is a relay or a Powerline Carrier (X-10)
device.
If Powerline Carrier Device (X-10) is selected, go to "A" prompt.
If relay is selected, skip to "B" prompt.
(prompt appears if X-10 is selected)
Enter the unit code (set at the device) and press [∗].
The system returns to the Output Number prompt.
(prompt appears if relay is selected)
Enter the predefined address for this module as listed below.
Make sure the module's DIP switches are set to the selected
address.
Module Addresses
Address
Module
07
1st 4229 (with zones 09-16)
08
2nd 4229 (with zones 17-24)
09
3rd 4229 (with zones 25-32)
10
4th 4229 (with zones 33-40)
11
5th 4229 (with zones 41-48)
12
1st 4204
13
2nd 4204
14
3rd 4204
15
4th 4204
† These addresses apply to VISTA-20P only.
This is the actual (or physical) relay number with respect to the
Relay Module upon which it is located. For 4204 modules, relay
numbers are 1-4. For 4229 modules, relay numbers are 1-2.
The system returns to the Output Number prompt for
programming the next device.
REMOTE SERVICES NOTE: If using the communication device's
multi-mode, program virtual 4204 relays to trigger on those
system events intended to be sent to the user's email address.
(4204 option = up to 4 events; 2-4204 option = up to 8 events)
– 26 –

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents