Access Code For Phone Module
∗ ∗ ∗ ∗ 28
00 = disable
1st digit: enter 1–9
2nd digit: enter # + 11 for "∗", or # + 12
for "#".
∗ ∗ ∗ ∗ 29
Enable IP/GSM? – Communication Device Menu Mode (pass-through programming)
This is a Menu Mode command, not a data field, for programming IP/GSM communication device options. See ∗29 Menu
Mode section later in this document.
Single Alarm Sounding Per Zone
∗ ∗ ∗ ∗ 31
0 = unlimited sounding
1 = one alarm sounding per zone
V20PSIA/V15PSIA:
"alarm sounding per zone" will be the
same as the "number of reports in
armed period" set in field *93 (1 if one
report, 2 if 2 reports, unlimited for
zones in zone list 7).
∗ ∗ ∗ ∗ 32
Fire Alarm Sounder Timeout
0 = sound stops at timeout selected in
field ∗33
1 = no timeout; sounds until manually
turned off
Alarm Sounder (Bell) Timeout
∗ ∗ ∗ ∗ 33
0 = none
1 = 4 min
2 = 8 min
Exit Delay
∗ ∗ ∗ ∗ 34
00 - 96 = 0 - 96 secs
97 = 120 secs
V20PSIA/V15PSIA:
45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result
in a 45-second delay.
∗ ∗ ∗ ∗ 35
Entry Delay #1
00 - 96 = 0 - 96 seconds
97 = 120 secs
98 = 180 secs
99 = 240 secs
V20PSIA/V15PSIA:
30-96 = 30 - 96 secs; 97 = 120 secs;
98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result
in a 30-second delay.
Entry Delay #2
∗ ∗ ∗ ∗ 36
See *35 Entry Delay 1 for entries.
∗ ∗ ∗ ∗ 37
Audible Exit Warning
0 = no; 1 = yes
V20PSIA/V15PSIA:
enabled; field does not exist.
(Partition 1 only)
You must assign a 2-digit access code for the 4286 Phone Module, if
used. Example: If desired access code is 7∗, then 7 is the first entry,
and [#] + 11 (for ∗) is the second entry.
NOTE: A 0 in either digit disables the phone module.
UL: must be 00 for UL Commercial Burg. installations
If enabled, limits alarm sounding on the bell output to once per zone
per armed period.
If "0" selected,
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances. Temporal pulse sounding for a
fire alarm consists of the following:
pulses.
UL: must be 1 for fire installations
3 =12 min
This field determines whether the external sounder will shut off after
4 = 16 min
time allotted, or continue until manually turned off.
UL: For residential fire alarm installation, must be set for a minimum of 4 min
(option 1); for UL Commercial Burglary installations, must be minimum 16 min
(option 4)
Part. 1
The system waits the time entered before arming entry/exit zones. If
the entry/exit door is left open after this time expires, an alarm will
occur. Common zones use same delay as partition 1.
SIA Guidelines: minimum exit delay is 45 seconds
Common zones use part. 1 delay.
UL installations: For UL Commercial Burglar Alarm and UL Residential Burglar
Alarm installations with line security, total exit time must not exceed 60
seconds.
Part. 1
Upon entering, the system must be disarmed before the time entered
expires, otherwise it sounds an alarm.
Common zones use same delay as part 1.
SIA Guidelines: minimum entry delay is 30 seconds
For UL Residential Burglary Alarm installations, must be set for a maximum of
30 seconds; entry delay plus dial delay should not exceed 1 min. For UL
Commercial Burglar Alarm, total entry delay may not exceed 45 seconds.
Upon entering, the system must be disarmed before the time entered expires,
otherwise it sounds an alarm.
Part. 1
Part. 1
Warning sound consists of slow continuous beeps until the last 10
Feature always
seconds, and then it changes to fast beeps. Sound ends when exit time
expires.
SIA Guidelines: must be enabled
|
[00]
[0]
[0]
[1]
|
|
[60,60]
Part. 2
|
|
[30,30]
Part. 2
|
|
[30,30]
Part. 2
[1,1]
Part. 2
– 6 –
3 pulses – pause – 3 pulses – pause – 3