O P E R A T I N G I N S T R U C T I O N S Flexi Classic Gateways...
Page 2
This document is protected by the law of copyright, whereby all rights established therein remain with the company SICK AG. Reproduction of this document or parts of this document is only permissible within the limits of the legal determination of Copyright Law. Alteration or abridgement of the document is not permitted without the explicit written approval of the company SICK AG.
Flexi Classic modular safety controller is integrated and who want to transmit data to a fieldbus (a controller) via a gateway. They are also addressed to people who are placing a Flexi Classic gateway in operation for the first time or maintaining it.
Pay attention to the safety notes and safety measures on the Flexi Classic safety controller! If the device is used for any other purposes or modified in any way — also during mounting WARNING and installation —...
The operating instructions must be made available to the operator of the machine where a Flexi Classic safety controller is used. The machine operator is to be instructed in the use of the device by specialist personnel and must be instructed to read the ope- rating instructions.
(X1-X4). A Flexi Classic gateway can only be operated on a Flexi Classic system. It does not have a dedicated voltage supply. It is only possible to use one Flexi Classic gateway per system.
High byte/low byte for the 16-bit checksum on the system configuration. The system configuration contains all function settings, the configuration jumpers, the number and order of the Flexi Classic modules inserted, the software versions etc. CRC1 and CRC2 together form the 16-bit checksum.
Logical error in the bypass function groups A and B (M = Bit mask; several errors can occur at the same time) On the occurrence of error codes other than those listed here, please contact the SICK Note technical hotline.
3.2.19 FUNCTION FUNCTION describes the setting of the rotary switch on the selected Flexi Classic module (not UE410-GU). This byte is to be interpreted differently depending on the module type, e.g. as program switch, switch for off delay or function switch.
Configuration jumper on S3 11 = Connected to +U 3.2.21 CRC_H CODE and CRC_L CODE High byte/low byte for the 16-bit checksum via the code area on the selected Flexi Classic module. Tab. 25: CRC_H CODE and Bit 7 Bit 0...
• The occurrence of random or systematic errors in the gateway or in its operation does Notes not result in the degradation of the safety functions on the Flexi Classic system. • With the operating voltage switched on, no gateways are allowed to be disconnected from the Flexi Classic system or added by plugging in.
MED13 – See also section 3.2 “Status information of all Flexi Classic gateways (system bytes)”. If a DP master is used that does not send any planning data to the UE410-PRO (e.g. PROFIBUS Master Simulator PR-MSV01 (6022458) from SICK in the “Start without GSD file”...
The occurrence of random or systematic errors in the gateway or in its operation does not result in the degradation of the safety functions on the Flexi Classic system. With the operating voltage switched on, no gateways are allowed to be disconnected from the Flexi Classic system or added by plugging in.
Input data module 4 MED5 Input data module 5 MED6 Input data module 6 See also section 3.2 “Status information of all Flexi Classic gateways (system bytes)”. 5.2.5 TxPDO2 Transmit PDO (process data object) 2. Tab. 41: Transmit PDO CAN-ID...
Output data module 7 MQD8 Output data module 8 MQD9 Output data module 9 See also section 3.2 “Status information of all Flexi Classic gateways (system bytes)”. 5.2.7 TxPDO4 Transmit PDO (process data object) 4. Tab. 43: Transmit PDO CAN-ID...
5.2.26 Flexi-Classic-ERROR list object This SDO contains a list of the ERRORs that have occurred in the Flexi Classic system. The list has 13 entries. The number of entries corresponds to the maximum number of Flexi Classic modules in the system.
The occurrence of random or systematic errors in the gateway or in its operation does Notes not result in the degradation of the safety functions on the Flexi Classic system. With the operating voltage switched on, no gateways are allowed to be disconnected from the Flexi Classic system or added by plugging in.
Configuration of the gateway — which data are transferred The UE410-EN3 processes the data of a UE410-EN3 Flexi Classic system and makes them available in different compilations, the data sets for the PLC. The configuration steps in this section are used to define which data sets are transferred to the higher-level PLC.
Page 60
Flexi Classic Gateways The installed Flexi Classic modules are recognised automatically and listed in the Flexi Chassis Configuration field. Modules of the next Flexi Classic generation that are not yet recognised by the UE410-EN3 are listed as “Unknown Module”. The corresponding front and the data structure of the module can be displayed by clicking a module.
VERSION_L, FUNCTION, KONF, CRC_H CODE and CRC_L CODE and transfers zeros into the corresponding data sets. Restarting the Flexi Classic system remedies this problem. Interrupt the power supply of the Flexi Classic system and switch on again. Troubleshooting Tab. 69: Troubleshooting...
The UE410-EN processes the data of a Flexi Classic system and makes it available in diffe- rent compilations, the data sets. These data sets are available over the TCP/IP interface.
VERSION_L, FUNCTION, KONF, CRC_H CODE and CRC_L CODE and transfers zeros into the corresponding data sets. Restarting the Flexi Classic system remedies this problem. Interrupt the power supply of the Flexi Classic system and switch on again. Troubleshooting Tab. 85: Troubleshooting...
Note system administrator. It can be read out in the administration pages of the DHCP server. Alternatively the software tool Flexi Classic IP-Link can be used. This scans the network for Flexi Classic modules and registers their IP addresses. Device name Device serial number as well as the device MAC address allow unique identification of the device.
Configuration of the gateway — which data are transferred The UE410-EN processes the data of a Flexi Classic system and makes them available in different compilations, the data sets for the PLC. There are 6 data sets available to this purpose: Data sets 1-5 contain fixed data compila- tions, Data set 6 can be configured by the user.
Page 101
After resetting the UE410-EN back to the factory settings, all modules are displayed as Note “Unknown Module” until a hardware reset of the entire Flexi Classic system has been carried out (see section “Resetting to factory settings” below). In order to use Data set 6, click Set 6. The following web page is displayed and shows the current compilation of Data set 6: Click Configure Set 6, to compile the user defined data record.
VERSION_L, FUNCTION, KONF, CRC_H CODE and CRC_L CODE and transfers zeros into the corresponding data sets. Restarting the Flexi Classic system remedies this problem. Interrupt the power supply of the Flexi Classic system and switch on again. Troubleshooting Tab. 110: Troubleshooting...
PROFINET IO Gateway Chapter 10 Operating Instructions Flexi Classic Gateways PROFINET IO Gateway The following Flexi Classic gateway can be used for PROFINET IO: UE410FEN4. The GSD file is available on www.sick.com. The UE410FEN4 supports: PROFINET IO conformance class A LLDP...
If the gateway IP address is unkown to the user or the IP address of the user’s PC shall not Note be changed, alternatively the software tool Flexi Classic IP-Link can be used to locate the gateway in the network and to configure the gateway’s IP address.
Page 124
– If a DHCP server is used to assign an IP address, the new address is unknown to the system administrator. It can be read out in the administration pages of the DHCP server. Alternatively the software tool Flexi Classic IP-Link can be used. This scans the network for Flexi Classic modules and registers their IP addresses.
STEP 2 — Add the gateway to the project In order to have the Flexi Classic system data available in the PLC process image, the gate- way must be added to the hardware configuration first. The procedure associated with this depends on the hardware configuration program of the PLC being used.
Page 128
Assign the device name to the gateway. Select PLC > Ethernet > Assign Device Name. The Assign device name dialog opens. From the Assign device name dialog, find and select the SICK gateway that you wish to assign the device name to in the list.
10.4.1 Cyclic data The physical Flexi Classic IO modules are not represented as typical hardware modules in the PROFINET IO hardware catalogue. Instead, the data available from the Flexi Classic system has been organized into data sets. Each data set represents a “hardware” module in the PROFINET IO hardware catalogue.
10.4.2 Acyclic data — record read Flexi Classic system diagnostic data is available as data record to be read by the PLC. There are two data sets, data set 5 and data set 6, providing diagnostic information. For a detailed description refer to Tab. 116 and Tab. 117 below.
Page 132
The installed Flexi Classic modules are recognised automatically and listed in the Flexi Chassis Configuration field. Modules of the next Flexi Classic generation that are not yet recognised by the UE410FEN are listed as “Unknown Module”. The corresponding front and the data structure of the module can be displayed by clicking a module.
Page 134
124 bytes. The minimum length is 0 (no data selected). This must be taken into account in regards to the size of the record read in the PLC. The selected data are transferred for all Flexi Classic modules respectively. The data are zeroed for modules that do not exist.
Alarms can be read acyclically through the PROFINET IO alarms infrastructure. Once any Flexi Classic module faults, the PROFINET IO gateway raises the appropriate diagnostic alarm to the network. This will trigger the fault LED on the PLC, and make the specifics (text and help) of the diagnostic alarm available through the SIMATIC PLC interface.
Click on Flexi System Status. The following web page is displayed: The page shows diagnostics for one Flexi Classic module at a time. The initial load of the page shows diagnostics of module 1 in the system. Module Type indicates the type of the module.
Page 139
Flexi Classic Gateways Via network tool The status of the Flexi Classic system can be verified from SIEMENS SIMATIC Manager, too. In order to do this follow the instructions below. Click Diagnostic/Setting in the PLC menu of the SIMATIC Manager tool bar.
VERSION_L, FUNCTION, KONF, CRC_H CODE and CRC_L CODE and transfers zeros into the corresponding data sets. Restarting the Flexi Classic system remedies this problem. Interrupt the power supply of the Flexi Classic system and switch on again. 10.7 Troubleshooting Tab. 119: Troubleshooting...
Internal flex-bus error: No frame bytes received in the slave. Check connection 0x10a between modules. Contact SICK service if problem persists. Internal flex-bus error: Data frame could not be sent. Power cycle Flexi Classic 0x110 system. Contact SICK service if problem persists.
Page 144
0x41b service. Self diagnostics error: Contact SICK service. 0x41c-0x4ff Internal input test error: Internal test pulse not present on Ix. Contact SICK service. 0x501-0x5ff External input test error: External test pulse not present on Ix. Check IO cabling. 0x601-0x6ff Contact SICK service if problem persists.
Page 145
0x986 switch settings, cabling and EDM settings. Configuration/diagnostics error: Rotary switch changed during operation. Restore 0x987 correct setting and power cycle Flexi Classic system or teach-in new setting. Configuration/diagnostics error: Incomplete data frame on IndexAssign. Contact 0x988 SICK service. Configuration/diagnostics error: Refer to the user manual for further details on 0x989-0x9ff this error code.