230-240 Volt Export Operation - Delfield F5MC36DV Installation, Operation And Maintenance Manual

F5 series; f15 series. refrigerated display cases
Table of Contents

Advertisement

Operation

230-240 Volt Export Operation

After turning the ON/OFF switch to ON the unit's
compressor will begin operating. Located on the operator
side at the top right is an ON/OFF switch for the display
lights.
Temperature Control
Display and base temperature is controlled by separate
thermostats. The display temperature control is located in
the fan shroud. The F15 base thermostat is located in the
mechanical compartment.
The thermostat is set at 2.5 at the factory to provide
proper operation.
To adjust the temperature, turn the knob clockwise as
indicated on the control. Settings are from 1 through 9
(9 being the coldest).
Adjustments should be made gradually.
Several small adjustments will be more effective than
one large adjustment.
It may take an hour or longer to realize the temperature
change depending on the application and location of
the unit.
Thermostat Dial
20
Export 230-240 Volt Pressure Control
The export display cases have a high pressure limiting
device. Under severe overloading conditions, or in the
event of a condenser fan failure or a plugged or blocked
condenser, this device may shut down the refrigeration
system. This device will automatically reset, but determining
the cause of the high pressure condition should be
investigated by a qualified refrigeration technician.
,
In attempting to adjust the pressure control, you can
do damage to your unit. Please contact KitchenCare +1
(844) 724-2273 or your local service agent. Delfield is
not responsible for charges incurred while having the
pressure control adjusted.
Factory Recommended Settings
Cut-in
Cut-out
Differential
Cut In -
Knob
Controlled
Di erential
F15 Refrigerated Base Evaporator Fan Operation
When the refrigerator is initially powered up or immediately
following a power outage the unit will begin cooling after a
3-6 minute delay. During normal operation the evaporator
fan pulses independently of the compressor as dictated by
the controller as follows:
During the cooling mode, compressor and evaporator
fan run simultaneously.
During the compressor off mode, evaporator fan pulses
three minutes on and three minutes off.
During an actual defrost event other than the off-cycle
defrost, compressor stays off but the evaporator fan
runs continuously.
Cooling Cycle
Compressor On
Compressor Off
Evaporator Fan On
Evap Fan Cycles On
3-Min, Off 3-Min
Section 3
Caution
20#
5#
15#
Defrost Cycle
Compressor Off
Evaporator Fan On
Part Number: 9291460 11/17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents