Operation
EVAPORATOR FAN OPERATION
During normal operation the evaporator fan may cycle
and/or pulse independently of the compressor. Consult
Technical Support at 1-844-724-CARE if you are unsure of
the proper function.
Cooling Cycle
Compressor On
Compressor Off
Evap Fan On
Evap Fan Cycles On
2-Min, Off 2-Min
18

115Volt F15 Pressure Control

F15 display cases have a high pressure limiting device.
Under severe overloading conditions, or in the event of a
condenser fan failure or a plugged or blocked condenser,
this device may shut down the refrigeration system. This
device will automatically reset, but determining the cause
Defrost Cycle
of the high pressure condition should be investigated by a
Compressor Off
qualified refrigeration technician.
Evap Fan On
In attempting to adjust the pressure control, you can
do damage to your unit. Please contact KitchenCare +1
(844) 724-2273 or your local service agent. Delfield is
not responsible for charges incurred while having the
pressure control adjusted.
Caution
,
Factory Recommended Settings
Cut-in
Cut-out
Differential
F15 Base Pressure Control
Part Number: 9291460 11/17
Section 3
20#
5#
15#