Installation
F5 Counter Installation For 36" & 48" Units
Installation Dimensions
Counter Cutout
2 Louver Cutouts
Max distance between counter
top and louver cutout
10
32.62" x 18.62" (83cm x 47cm)
22" x 11" (56cm x 28cm)
4.00" (10cm)
Air duct dimensions
to match condenser face
13.00"
(33cm)
11.00"
(28cm)
4.0" (10cm)
Max
11.00"
(28cm)
1. Install partitions between F5 refrigerated display case
and other electrical appliances if they are located in the
same cabinet. Partitions must fully extend front to back
and top to bottom.
2. Install a GFCI receptacle a minimum of 14" (36cm) up
from the cabinet bottom inside the partitions.
3. The unit requires airflow to the compressor. Two
louvers are provided with each unit.
NOTE: Any restriction to the proper air flow will void the
compressor warranty.
Louver cut-outs are 22" x 11" (56cm by 28cm).
143in2 (923cm2) is required at both the intake and
discharge.
Cut-outs are to begin a maximum of 4.00" (10cm)
from the counter-top.
Install the louvers on the front and back of the
cabinet.
Discharge Air
Condenser
Fresh Air
4. Place the condensing unit through the counter cutout.
5. Construct a 13" x 11" (33cm x 28cm) air duct (not
provided) connecting the condenser face to the louver.
This will prevent recirculation of discharge air.
Air duct dimensions
to match condenser face
13.00"
(33cm)
Section 2
Louver
Louver
11.00"
(28cm)
Part Number: 9291460 11/17