Counter Installations - Delfield F15 Series Specifications, Installation, Operation & Maintenance Manual

Table of Contents

Advertisement

Installation
F5 Counter Installation
For any non-standard installation consult the factory.
1. Cabinet interior minimum dimensions:
Dimension
A
B
C
D
E
F
2. Place the condensing unit through the counter cutout.
3. Extend the telescoping duct from the front of the
condensing unit to the back of the louver. This will
prevent recirculation of discharge air. Export models do
not have a telescoping duct, skip to step 6.
4. Put eight provided screws through the telescoping
duct side walls to hold it at the desired depth.
Use Screws to Secure Desired
3 of 8 Screws Shown
12
All
29.75"/ 75.5cm
30"/ 76cm
28"/ 71cm
24"/ 61cm
19"/ 48cm
Min - 5.5"/ 14cm
Max - 9.5" / 24cm
Depth
5. Partitions must fully extend front to back and top to
bottom.
6. Louver cutout must extend to bottom of cabinet and
align with condenser face.
NOTE: The louver provided must be installed in front of
the condensing unit's finned coil. Any restriction to the
proper air flow will void the compressor warranty.
Louver measures 20.00" x 25.00" (51cm x 64cm).
Louver Cutout Size is 18.50" x 22.50" (47cm x 57cm)
(typical installation).