Air Supply
Action
Supply Pressure
Air Delivery
Air Capacity
(flow coefficient)
Air Consumption
Air Supply Failure
Loss of Input Signal
Output Pressure
© 2016 General Electric Company. All rights reserved
Table 11: Pneumatics Single Acting Standard Flow
Dry, oil-free, 5 micron filtered air (per ISA S7.3)
Direct Acting
15 to 100 psi max. (1.03 to 7 Bar)
Regulate 5 psi minimum above actuator spring
range. Do not exceed actuator rating.
10.0 scf/min (283 L/min.) at 30 psi (2.1 bar) supply
16.6 scf/min. (470 L/min.) at 60 psi (4.2 bar) supply
23.3 scf/min. (660 L/min.) at 90 psi (6.3 bar) supply
Loading
CV = 0.30
Venting
CV = 0.40
0.19 scf/min. (5.4 L/min.) at 30 psi (2.1 bar) supply
0.30 scf/min. (8.5 L/min.) at 60 psi (4.2 bar) supply
0.40 scf/min. (11.4 L/min.) at 90 psi (6.3 bar)
supply
On supply failure the actuator output fails to
atmosphere. Some overshoot may occur when
air pressure returns after a period without air
supply pressure.
Actuator Output fails to atmosphere
0-100 psi (6.9 bar) max
.
Masoneilan SVi1000 Positioner Quick Start Guide =| 69