Installation; Inspection; Handling; Vibration Isolators - Daikin SWP Series Installation Manual

Self-contained air conditioning systems
Table of Contents

Advertisement

Inspection

When the equipment is received, carefully check all items
against the bill of lading to ensure a complete shipment . Do
not sign the shipping receipt until all items are accounted for .
Carefully inspect all units for damage upon arrival . Report
all shipping damage to the carrier and file a claim. Before
unloading the unit, check the unit serial plate to be sure it
agrees with the power supply available .
NOTE: Check for concealed damage as soon as possible .

Handling

Never allow any part of the unit to fall during unloading or
moving as this can cause equipment damage, severe
personal injury, or death .
Do not attempt to install dollies in the center of the unit . Units
can become unstable and tip over, causing injury
Do not move units in an upended position . Internal components
may tear away, causing injury .
Units ship with a protective covering that should remain in
place while the unit is being moved to its final location.
Units are provided with lifting lugs for rigging with a crane . If
units are lifted by crane, use slings or cable to protect against
chaffing damage and use spreader bars across the top of the
cabinet to prevent any structural damage to the frame .
The unit base frame accepts dollies or Johnson bars for
transporting the unit . Place furniture dollies at all lift point
locations and use a Johnson bar at one end for maneuvering .
IM 1032-2 • Self-Contained Air Conditioning System
WARNING
CAUTION
CAUTION

Vibration Isolators

All units are provided with 1" neoprene isolation pads, shipped
separately . Using the instructions provided in the shipment,
install pads beneath the unit, locating them at each corner and
at 1/2 the length of each side base channel . Evenly space the
additional pads under the remaining base channels .
NOTE: Only qualified personnel familiar with local codes
and regulations and experienced with this type
of equipment should perform installation and
maintenance
Figure 2: Isolation Pad Placement
(1/2)L
(1/2)L
4
I
nsTallaTIon
I
nsTallaTIon
www .DaikinApplied .com

Hide quick links:

Advertisement

Table of Contents
loading