Daikin SWP Series Installation Manual page 9

Self-contained air conditioning systems
Table of Contents

Advertisement

Table 3: Maximum Weights of Individual Sections (lbs.)
Condenser/
Unit Size
Compressor
Small
1850
Small Tall
2250
Medium
2450
Large
2550
Large Tall
4300
8 Compressor
4500
Figure 9: Condenser/Compressor Section and Coil Section
Ready for Separation
Cut Liquid and Suction
Lines and Remove the
Victaulic Coupling
Victaulic
Coupling on
Water Pipe
Figure 10: Coil Section and Compressor/Condenser
Section
Arrows show lifting
bracket locations
www .DaikinApplied .com
Control
Coil
Fan
Panel
1750
1200
1900
1450
2550
1850
3000
2450
3550
2900
3550
3250
Suggested
Cutting Area
for Refrigerant
Lines
3/8" Hexagon Head Bolts
Sections are hinged
with chains and
spreader bars for lifting
Reassembly
1 . Starting with the coil/access section, attach the double
galvanized steel plates to the base .
300
2 . Line up the compressor/condenser section with the coil/
300
access section . Slide the compressor/condenser section
400
towards the coil section . Attach the two sections using
450
the double galvanized steel plates . Install painted steel
500
plates (flat) in their respective areas.
650
3 . Braze the refrigerant (liquid and suction) lines between
two sections (Note: R410A design working pressure is
450 PSI . or as indicated on the unit data label) . Similar
factory joints are brazed with Copper-Phosphoros-2%
Silver brazing rods .
4 . Connect water pipes using the Victaulic couplings . Test
water pipes for leaks in areas with new connections . Test
refrigerant pipes for leaks in new brazed areas .
5 . Evacuate, test and charge the refrigerant circuits with
R410A . See dataplate for refrigerant charge amount per
circuit .
6 . Lift the supply fan section taking care to align the splice
joint to seat into the mating gasket of the coil/access
section to provide an air tight seal . All corners of the unit
sections must line up before some of the flat and right
angle steel plates can be installed to stabilize the fan,
coil and compressor/condenser sections together .
7 . All units have shipping brackets holding the fan tight
in place during shipping . Remove brackets before
commissioning the fan section and adjust the spring
isolators before installing the control panel box .
8 . Organize all wire harnesses in each section and get
them ready to reconnect to the Control Panel .
9 . Lift the Control Panel into place . Attach the section using
painted flat and right angle steel plates
the control box is secure, re-connect power wires, control
plugs and sensors .
Keep your hands at a safe distance from the unit while guiding
the wires into the control panel during installation . Make sure
no wire get caught under the Control panel box frame .
Re-install interconnecting wires only, after the panel has been
set and secured .
9
IM 1032-2 • Self-Contained Air Conditioning Systems
I
nsTallaTIon
(Figure
5) . After
CAUTION
WARNING

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents