Performance Data
Note
To allow module replacement without a PG, settings on the CPU must be
modified. Open the Properties dialog of the CPU in HW Config; in the "Monitoring
time for" box in the "Startup" tab, check and, if necessary, modify the following
values:
– "Transfer of parameters to modules" (recommended value = 600 *100 ms)
Depending on your system (station configuration), you may need to increase the
following parameter:
– "Ready message from modules"
For more detailed information about supported services and parameters, refer to
the PICS tables (PICS: Protocol Implementation Conformance Statements) in the
manual /4/.
5.4

Characteristics of S7 Communication

The following data are important for operating S7 connections:
Table 5-5
Characteristic
Number of S7 connections that can
be operated via PROFIBUS
B3–16
www.gkbpx.com
Explanation / Values
Maximum 48
(The value depends on the S7-400 CPU being used.)