Honeywell 301C User Manual page 78

Controller unit
Hide thumbs Also See for 301C:
Table of Contents

Advertisement

Available languages

Available languages

IAQPoint2 continued
Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Storage
1
Data Type
Required
Type
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
BACnet
2
Writeable?
Sensor number * 256 + 1. Sensor number
for RH is Modbus address + 2. For example
C
N
an IAQPoint2 at Modbus address 005 will
appear as 1793 or 0x0701.
C
N
analog_input (0)
if temp sensor fault, fault (1),
R
N
else normal (0)
"IAQPoint RH AdXXX .RH" where XXX is
N
N
the Modbus address plus two.
R
N
FALSE
R
N
Relative Humidity in percent
As appropriate reports
no_fault_detected (0) or
R
N
no_sensor (1) or
unreliable other (7)
Fault is detected within 60 seconds
if not purchased or faulty "true" (1)
R
N
else "false" (0)
if not purchased or faulty "true" (1)
R
N
else "false" (0)
C
N
False (0)
R
N
False (0)
N
N
percent_relative_humidity (29)
78
Value
continued...

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents