Xnx And Xcd - Honeywell 301C User Manual

Controller unit
Hide thumbs Also See for 301C:
Table of Contents

Advertisement

Available languages

Available languages

XNX and XCD

Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
1
Data Type
Required
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
Storage
BACnet
2
Writeable?
Type
Modbus address * 256 + 1. For example an
C
N
XNX at Modbus address 010 will appear as
2561 or 0x0A01.
C
N
analog_input (0)
if gas sensor fault Fault (1),
R
N
else normal (0)
"SSS GGGG AdAAA.GGGGG" where SSS is
the sensor type, GGGG is the gas name and
AAA is the Modbus address. Gas names are
truncated to 4 and 5 characters. Values for
N
N
sensor type are "XNX" or "XCD" For
example, an XNX at address 10 with a
Methane sensor will populate this object
name with "XNX Meth Ad010.Metha"
R
N
FALSE
R
N
Gas reading
As appropriate reports
no_fault_detected (0) or
R
N
unreliable other (7)
Fault is detected within 60 seconds
if faulty "true" (1)
R
N
else "false" (0)
if faulty "true" (1)
R
N
else "false" (0)
R
N
"false" (0)
R
N
"false" (0)
96 (ppm) or
N
N
98 (percent) or
95 (no_units)
86
Value
continued...