Honeywell 301C User Manual page 201

Controller unit
Hide thumbs Also See for 301C:
Table of Contents

Advertisement

Available languages

Available languages

EC-FX (suite)
Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
1
Data Type
Required
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
Storage
BACnet
2
Writeable?
Type
Modbus address * 256 + 6. For example an
N
N
EC-F9 at Modbus address 003 will appear as
774 or 0x0306.
C
N
analog_value (2)
C
N
normal (0)
"EC-F9 GGGG AdXXX.Cmin" where GGGG is
N
N
the gas name and XXX is the Modbus
address. The gas name is often "NH3".
C
N
FALSE
Gas threshold. Synchronization is
maintained with the 301C and the EC-F9.
N
Y
Whichever value is written last is
distributed to the other two locations.
C
N
no_fault_detected (0)
C
N
always false (0)
C
N
always false (0)
C
N
always false (0)
C
N
always false (0)
C
N
Usually ppm (96)
Modbus address * 256 + 7. For example an
N
N
EC-F9 at Modbus address 003 will appear as
775 or 0x0307.
C
N
analog_value (2)
C
N
normal (0)
"EC-F9 GGGG AdXXX.Cmax" where GGGG is
N
N
the gas name and XXX is the Modbus
address. The gas name is often "NH3".
C
N
FALSE
Gas threshold. Synchronization is
maintained with the 301C and the EC-F9.
N
Y
Whichever value is written last is
distributed to the other two locations.
C
N
no_fault_detected (0)
C
N
always false (0)
C
N
always false (0)
C
N
always false (0)
C
N
always false (0)
C
N
Usually ppm (96)
201
Value

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents