IAQPoint2 continued
Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Storage
1
Data Type
Required
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
BACnet
2
Writeable?
Type
Modbus address * 256 + 4. For example an
N
N
IAQPoint2 at Modbus address 005 will
appear as 1284 or 0x0504.
C
N
analog_value (2)
C
N
normal (0)
IAQPoint CO2 AdXXX .Bmin" where XXX is
N
N
the Modbus address.
C
N
FALSE
Gas threshold. This is copied from the
sensor via the 301C. BACnet permits
N
Y
writing. But this has no effect and the
value reverts in a few seconds.
C
N
no_fault_detected (0)
C
N
always false (0)
C
N
always false (0)
C
N
always false (0)
C
N
always false (0)
if CO2 fitted, ppm (96)
C
N
if VOC fitted, %
Modbus address * 256 + 5. For example an
N
N
IAQPoint2 at Modbus address 005 will
appear as 1285 or 0x0505.
C
N
analog_value (2)
C
N
normal (0)
IAQPoint CO2 AdXXX .Bmax" where XXX is
N
N
the Modbus address.
C
N
FALSE
Gas threshold. This is copied from the
sensor via the 301C. BACnet permits
N
Y
writing. But this has no effect and the
value reverts in a few seconds.
C
N
no_fault_detected (0)
C
N
always false (0)
C
N
always false (0)
C
N
always false (0)
C
N
always false (0)
if CO2 fitted, ppm (96)
C
N
if VOC fitted, %
80