E³Point continued
Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
polarity
present_value
priority_array
reliability
relinquish_default
active_text
inactive_text
status_flags
in_alarm
fault
overridden
out_of_service boolean
object_identifier
object_type
event_state
object_name
out_of_service
polarity
present_value
priority_array
reliability
relinquish_default
status_flags
in_alarm
fault
overridden
out_of_service boolean
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Storage
Data Type
1
Required
R
enumerated
R
enumerated
R
character string
R
boolean
R
enumerated
R
enumerated
R
R
enumerated
0
R
character string
O
character string
O
boolean
R
boolean
R
boolean
R
R
R
enumerated
R
enumerated
R
character string
R
boolean
R
enumerated
R
enumerated
R
R
enumerated
0
R
boolean
R
boolean
R
boolean
R
R
BACnet
2
Writeable?
Type
Modbus address * 256 + 8. For example an
C
N
E3Point at Modbus address 009 will appear
as 2312 or 0x0908.
C
N
binary_output (4)
C
N
normal (0)
"E3POINT GGGG AdXXX .rel1" where
GGGG is the gas name and XXX is the
N
N
Modbus address. Values for gas name
include "CO" and "COMB".
C
N
FALSE
C
N
always Normal (0)
Reading this reports the true state of the
R
Y
buzzer. Mixing BACnet and event control of
this output is not supported.
R
N
last value written
C
N
no_fault_detected (0)
C
N
not meaningful.
C
N
"ON"
C
N
"OFF"
C
N
always "false" (0)
C
N
always "false" (0)
R
N
always "false" (0)
R
N
always "false" (0)
Modbus address * 256 + 9. For example an
C
N
E3Point at Modbus address 009 will appear
as 2313 or 0x0909.
C
N
binary_output (4)
C
N
normal (0)
"E3POINT GGGG AdXXX .rel2" where
GGGG is the gas name and XXX is the
N
N
Modbus address. Values for gas name
include "CO" and "COMB".
C
N
FALSE
C
N
always Normal (0)
Reading this reports the true state of the
R
Y
relay. Mixing BACnet and event control of
this output is not supported.
R
N
last value written
C
N
no_fault_detected (0)
C
N
not meaningful.
C
N
always "false" (0)
C
N
always "false" (0)
C
N
always "false" (0)
C
N
always "false" (0)
85