Iaqpoint2 - Honeywell 301C User Manual

Controller unit
Hide thumbs Also See for 301C:
Table of Contents

Advertisement

Available languages

Available languages

IAQPoint2

Group
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service boolean
units
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --
'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Storage
1
Data Type
Required
Type
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
R
enumerated
R
enumerated
R
character string
R
boolean
R
real
R
enumerated
O
boolean
R
boolean
R
boolean
R
R
enumerated
R
BACnet
2
Writeable?
Modbus address * 256 + 1. For example an
C
N
IAQPoint2 at Modbus address 005 will
appear as 1281 or 0x0501.
C
N
analog_input (0)
if gas sensor fault Fault (1),
R
N
else normal (0)
"IAQPoint CO2 AdXXX .CO2" where XXX is
N
N
the Modbus address.
R
N
FALSE
Gas reading
R
N
if CO2 fitted, 0 to 5000
if VOC fitted, 0 to 100
As appropriate reports
no_fault_detected (0) or
R
N
no_sensor (1) or
unreliable other (7)
Fault is detected within 60 seconds
if faulty "true" (1)
R
N
else "false" (0)
if faulty "true" (1)
R
N
else "false" (0)
R
N
"false" (0)
R
N
"false" (0)
if CO2 fitted, ppm (96)
N
N
if VOC fitted, %
Sensor number * 256 + 1. Sensor number
for temperature is Modbus address + 1. For
C
N
example an IAQPoint2 at Modbus address
005 will appear as 1537 or 0x0601.
C
N
analog_input (0)
if temp sensor fault, fault (1),
R
N
else normal (0)
"IAQPoint ToC AdXXX .ToC" where XXX is
N
N
the Modbus address plus one.
R
N
FALSE
Temperature reading in Celcius, regardless
R
N
of IAQPoint2 configuration.
As appropriate reports
no_fault_detected (0) or
R
N
no_sensor (1) or
unreliable other (7)
Fault is detected within 60 seconds
if not purchased or faulty "true" (1)
R
N
else "false" (0)
if not purchased or faulty "true" (1)
R
N
else "false" (0)
C
N
False (0)
R
N
"false" (0)
N
N
Celcisus (62)
186
Value
(98)