(2) Make the following settings to perform tracking.
(Tracking is performed when the operation mode is switched to other than CAS, CSV or CCB.)
For 2-degree-of-freedom PID (S.2PID), set the following operation constant items to specify tracking.
Setting item
Tracking bit (TRK)
Set value pattern (SVPTN)
5.2.3

Loop selector tracking

Tracking is performed under the following conditions.
• The operation mode is any of MAN, CMB, CMV and LCM and the tracking bit (TRK) is 1
• When the operation mode is any of AUT, CAS, CAB, CCB, CSV, LCA and LCC
The tracking bit (TRK) is 1 and BB1 of BB is 1
Process value
(PV1)
Process value
(PV2)
Example) When the S.SEL instruction uses the input value E1 and E1 uses the upper loop (loop 0) MV, the S.SEL
instruction's MV is trucked to loop 0's MV.
The setting that conducts Tracking is shown below.
Operation constant
Tracking bit
Set value pattern
1 (Tracking performed)
Set value pattern
0 (Set value is upper loop MV.)
Set value Used
0 (E2 is used)
Loop tag memory
S.IN
S.PHPL
S.2PID
Loop 0
Loop 1
S.IN
S.PHPL
S.2PID
Loop tag memory
S2
+4
1
0
1
0
+5
Setting
Manipulated
value (MV)
Tracking
E1
S.OUT1
S.SEL
S.OUT1
E2
Manipulated
value (MV)
1
0: Tracking not performed.
1: Tracking performed.
0
Input value selection
0: E1 is selected.
1: E2 is selected.
Input value (E1) use
0: E1 is used.
1: E1 is not used.
Input value (E2) use
0: E2 is used.
1: E2 is not used.
Input value (E1) pattern
0: E1 is upper loop MV.
1: E1 is not upper loop MV.
Input value (E2) pattern 0: E2 is upper loop MV.
1: E2 is not upper loop MV.
1
2
3
4
5
6
7
8
37