Specified position
Symbol
+20
ML
+21
+22
SV1
+23
Loop tag
+52
SV16
*2
+53
memory
+54
MV1
+55
+84
MV16
+85
*1
The data of the item(s) where the values within the recommended range are given in the parentheses are stored by the
system. Users cannot set the data.
*2
The loop tag memory and loop tag past value memory occupy a total of 128 words. (Refer to Page 27, Section 3.3.1 for
details.)
(2) Execution cycle ( T)
Set the execution cycle in SD1500 and SD1501 as real numbers.
Set Data
Processing contents
(1) Output type
The output type is determined by the combination of the operation mode (MODE) and operation type (TYPE) as
indicated below.
Operation mode (MODE)
MAN, CMB, CMV, LCM, LCA, LCC
AUT, CAB
CAS, CCB, CSV
(2) Loop stop processing
(a) Setting 1 in SPA of the alarm detection (ALM) selects a loop stop.
A loop stop performs the following processing and terminates the S.PGS instruction.
1) BW retains the last value.
2) MHA and MLA of the alarm detection (ALM) are turned to 0.
3) The operation mode (MODE) is changed to MAN.
4) BB1 to BB3 of BB are turned to 0.
(b) Setting 0 in SPA of the alarm detection (ALM) selects a loop run.
A loop run performs "(3) SV count-up processing".
Name
Recommended range
Output lower
-10 to 110
limit value
Setting time 1
0 to 999999
Setting time
16
Setting output
1
-10 to 110
Setting output
16
Operation type (TYPE)
––
0
1
––
*1
Unit Data format
Real
%
number
Real
s
number
Real
%
number
Operation
Operation stopped at current SV and MV
Hold type operation
Return type operation
Cyclic type operation
S.PGS
Standard
Set
value
by
9
0.0
U
2
0.0
U
3
0.0
U
4
4
6
7
8
191