Chapter 2 - Installation

A - Handling

The CP Compressors must always be handled with care. It may
be lifted either with a forklift truck or by means of a travelling
crane. In the latter case, precautions must be taken in order not to
damage the unit's canopy.

B - Room

The CP Compressors is designed to operate in a frost-free
environment, supplied with air at a temperature of no more than
104 °F. The premises must be well-aired and as close as possible
to the place where the compressed air is used. A space must be
left around the unit, for cleaning and maintenance purposes. It is
very important for the compressor to have an abundant supply of
fresh air. (see page 2).
COMMENT
When the atmosphere is contaminated by organic or mineral dust or
by corrosive chemical emanations the following precautions must be
taken:
1. Provide another air inlet as close as possible to the
compressor suction.(recommendation which is valid if the
only room available is excessively damp).
2 - Use an additional air supply filter. Consult us.
Installation with heat dispersion sleeve
If the operation of the compressor increases the ambient
temperature above 104°F, it is necessary to discharge the hot air
leaving the cooler to the exterior by means of a sleeve.
V
L
Compressor
Fig. 5a - Sleeve with roof outlet
d
Ventilation Duct minimum cross section
flow rate
cfm
CPF 175
11780
CPVS 200
16485
CPF 200
16485
CPVS 250
16485
Chicago Pneumatic Compressors
62 305 799 65
Prevailing wind
Flexible fitting
( d ≤ L ≤ 1,6d )
sqm
10.87
15.22
15.22
15.22
Fig. 5b - Sleeve with an elbow
V maxi = 18,04 ft/s
(Ratio of volume flow rate of the ventilation to the sleeve
cross section)
L maxi = 32.8 ft (without mechanical extractor)
Cross section of room air inlet > 2 x Duct outlet cross section
2 elbows accepted with large radius of curve and fluid gui-
dance vanes
Ratio (Length/Width of sleeve) maxi = 1.6
Make sure that no outside air, especially if humid, can be fed
back into the machine and damage electric and electronic
components or rust metal parts.
The maximum admissible pressure loss of the sleeve should not
exceed 30 Pa (3 mmCE). In case of higher value, provide an
additional ventilation (mechanical extractor) with a flow
equivalent to that of the machine, C1 converter controlled (see
electrical diagram).
Regulation type 0-10V
0V extractor shutdown
10V full rate operation

C - Assembly

Put the unit on a stable surface. The CP does not need foundations.
Any flat surface that can support their weight will be sufficient
(industrial floor).

D - Air discharge pipes

The diameter of the air discharge pipe must be at least 3" gas for
the CPF 175/200 and CPVS 200/250.Current legislation requires
that a valve which is lockable in the closed position be installed
at the air box outlet, connected to the compressor by a union
and flexible line to allow it to be cut off during repair work.
Prevailing wind
L
Flexible fitting
V
Compressor
11/2008
Page 9