Address Registers Format
41067
2
41069
2
41071
2
41073
2
41075
2
2
2
41083
2
2
41085
6
3
44001
4
1 per
44007
interval
5
2 per day Custo
45501
6
8
46025
7
8
46049
46057
8
46513
8
46521
8
1. To clear single meter kWh/kVARh, set multiple points at 40001 or 41001 for 8
points with data set to 0000 0000 0000 0000 0000 0000 0000 0000. Remove
Jumper J6 after changes have been made.
2. External inputs are standard on Class 5000 meters and optional on Class 3400
meters (Part of Expanded Feature Package).
To clear external inputs, set multiple points at 41083 or 41085 for 2 points with
data set to 0000 0000. Jumper J6 must be closed. Remove Jumper J6 after
changes have been made.
3. To set the interval data day block, set multiple points at 44001 for 6 points with
data set to 0C0I 0000 MMDD YYYY 0000 0000.
0C = Channel, 0I = Interval (0F = 15 minute intervals, 05 = 5 minute intervals)
4. Each register represents a 15 or 5 minute kWh pulse value based on the
interval day block. 96 registers max with 15 minute intervals. 288 registers max
with 5 minute intervals. The first interval data register 44007 represents the
pulse count for the first 15 or 5 minute interval beginning at midnight.
5. The interval data headers represent days with available interval data. Each day
represents 2 registers. Format: MMDD YYYY.
6. To set the date and time, set multiple points at 46025 for 4 points with data set
to HHMM SSDW MMDD YYYY (DW=day of week)
7. To change the ModBus ID, set single point at 46050 with data set to new
ModBus ID (e.g. 1 to 247). Jumper J6 must be closed.
ModBus Customer Point Map: CL3400
Float
Voltage, line to line, phase B-C Volts-L
Float
Voltage, line to line, phase C-A Volts-L
Float
Phase angle, phase A
Float
Phase angle, phase B
Float
Phase angle, phase C
Float
External Input 1
Float
External Input 2
Custo
Interval Day Block
m
Integer Interval Data
Interval Data Headers
m
Custo
RTC Date/Time
m
Custo
EZ7 ID, ModBus ID, Serial
m
Number
Custo
Recorder Info., Demand
m
Interval
Custo
Flags L1: Power Failure,
m
Battery
Custo
Flags L2: Power Failure Date
m
51
E-MON CLASS 3400 METER
Description
CL
Units
3400
R
R
Degree
R
Degree
R
Degree
R
Pulse
R/W
Pulse
R/W
R/W
Pulse
R
R
R/W
R/W
R/W
R
R
62-0398—02