E-MON CLASS 3400 METER
10.2.3 IP Setting Display Screen
To Change the IP settings, complete the following steps:
1. Press the MENU button.
2. The following screen will appear:
—> LOAD CONTROL
DATE & TIME
DEVICE ID
IP SETTINGS
3. Use UP or DOWN button until the arrow is on the IP Setting line.
LOAD CONTROL
DATE & TIME
DEVICE ID
—>IP SETTINGS
4. Press the SELECT button. The IP Setting Screen will appear.
ENABLE DHCP?N
IP: 192.168.0.168
MSK:255.255.2550
GWY:192.168. 0.1
5. Locate the number to be changed in the menu, press and hold Button 4
(Down Button) for 3 seconds, release the button, the last digit for this num-
ber blinks,;
6. To change the number of the digit, use Button 3 (Up Button) to cycle
through 0 to 9.
7. Press Button 4 to move to the next digit, and repeat Step 5.
8. To exit the mode of changing number by digit, press Select Button;
9. To save the new number, press Main Menu Button and select "Y" to save.
Save changes: Y / N
This will also return you to main menu. In main menu, select EXIT to get out of
programming mode and return to normal display mode.
62-0398—02
NOTE: The menu items that can be
changed by digit are: IP address/
Gateway/Subnet Mask, BACnet
Device ID, BACnet MSTP MAC
Address/max masters, Modbus ID,
and dollar cost/CO2 lbs for Green
Net meters.
44