E-MON CLASS 3400 METER

6.13 Ethernet Communications

Ethernet/IP communications connections are provided through an RJ-45
connector(J8) in the lower right corner of the main power board. This port can be
connected directly to a network port of a PC using a Cat. 5e crossover cable.
Two LEDs are provided directly above the connector. The LINK LED is yellow and
when lit, indicates ethernet connectivity. The ACT led is green and when lit,
indicates communication activity.
The communication protocol for the Ethernet port is selected when ordering the
meter. The available choices are EZ7, Modbus TCP/IP and BACnet IP. See the
ordering information for the available choices in combination with the RS-485
output.
E- Mon Class 3400 Meters can be tied into a local Ethernet network individually.
Multiple RS-485 meters to Ethernet requires optional "EKME" device. Each
device that is connected directly to the ethernet network requires a unique IP
address.
SEE SECTION 10 FOR INSTRUCTIONS ON CHANGING ID AND IP ADDRESSES.
RS-485 DAISY CHAIN (SECTION 5.7)
Fig. 17. EMS or Control Unit with Modbus Communication RS-485 Daisy
62-0398—02
Chain Ethernet Network.
32
EMS OR WEBs
CONTROLLER
CONNECTION VIA
DAISY CHAIN RS-485
M34371
ETHERNET
NETWORK
M34373