PROFIBUS-DP Master DTM
Item
Description
Baud rate
Defines the transmission rate on the PROFIBUS-DP Network. The following baud
rate values are defined by the PROFIBUS-DP standard:
• 9.6 kBits/s
• 19.2 kBits/s
• 45.45 kBits/s
• 93.75 kBits/s
• 187.5 kBits/s
• 500 kBits/s
• 1500 kBits/s
• 3000 kBits/s
• 6000 kBits/s
• 12000 kBits/s
The default value is 1500 kBits/s.
Optimize
The Optimize setting defines whether or not selected parameters can be changed
by the user.
• By Standard
• By User
Note 1. If the By User option is selected and changes have been made, it is
Slot Time
The maximum time a Master Unit must wait for a response to a request message.
Min. Station Delay
The minimum allowed time for a slave station before it will generate a response to
of Responders
a request message.
Max. Station Delay
The maximum allowed time for a slave station to generate a response to a
of Responders
request message.
Quiet Time
The time a transmitting station must wait after the end of a message frame,
before enabling its receiver.
Setup Time
The time between an event and the necessary reaction.
Min. Slave Interval The Minimum Slave Interval defines the poll cycle, i.e. the minimum time between
two consecutive Data_Exchange Cycles to the same slave station. The Minimum
Slave Interval must be smaller than the Target Rotation Time.
Calculated Minimum Slave Interval in milliseconds.
Target Rotation
The anticipated time for one token cycle, including allowances for high and low
Time
priority transactions, errors and GAP maintenance. Do not change the value
below the calculated value, to avoid bus communication interruptions.
Max Retry Limit
Maximum number of request transmission retries by this master if a station does
not reply to a request.
Highest Station
The HSA defines the Highest Master station address on the network, of which the
Address
Master station will request the FDL status, when updating the active station list
(See GAP Update Factor).
Shows the station address of the master. If new slaves are added to the network,
this field shows the highest station address.The Master will periodically check
whether new active stations have been added between address its own address
and the Highest Station Address. If any stations are detected, GAP is updated.
Permissible values are in the range of 2 to 126.
The table below lists the Bus Parameters, which are shown in the Bus Param-
eter tab.
Forces the user to use the default (optimized) settings.
Makes selected fields editable.
still possible to switch between Optimize settings, without the changes
being lost.
2. If the By User option is selected and the baud rate is changed, the pa-
rameters will be optimized to the new baud rate.
Section 3-3
Unit
Editable
by User
--
Yes
--
Yes
t
Yes
BIT
t
Yes
BIT
t
Yes
BIT
t
No
BIT
t
No
BIT
t
Yes
BIT
ms
No
t
Yes
BIT
--
Yes
--
Yes
65