Configurator Error and Warning Messages
Number
Message
08
Set Parameters failed. Slave can-
not be configured
09
No slaves assigned. Download
aborted.
10
Slave(s) has no modules. Down-
load aborted
11
Configured EM bank (banks) is
not available in the connected
PLC.
Download aborted
12
Connected unit is busy. Download
aborted.
E-3
Error Messages - Communication
The table below lists the Error messages related to CX-Server communication between the PROFIBUS-DP
Master Unit DTM and the PLC.
Number
Message
50
Communication Failure with Unit
51
Communication Failure with PLC
Description
An internal error has occurred pre-
venting the master DTM from set-
ting/changing the slave's bus
address.
No slaves have been assigned to the
master. At least one slave must be
assigned.
A slave (or slaves) has no modules.
The configured EM bank (banks) are
not available in the connected PLC.
Unit is busy with parameter storage. Retry download when parameter
Description
The communication between the PC
and the Unit on the PLC could not be
achieved.
The communication between the PC
and the PLC could not be achieved.
Appendix E
Correction
Non recoverable. Master DTM tries
to assign a new bus address to the
slave DTM, but the slave DTM's
database is locked.
Retry download when at least one
slave has been assigned.
Retry download when modules have
been added to the slave(s) having
no modules.
Change the configuration to use only
memory areas available in the PLC
and retry download.
storage has finished.
Correction
Ensure there are no problems
with the connection between the
Personal Computer and the PLC.
Ensure the Master Unit has been
correctly mounted - Refer to sec-
tion 2-2 Installing the PROFI-
BUS-DP Master Unit for detailed
information.
Make sure the Device settings
are correct.
Perform one of the following suc-
cessfully to confirm the problem
has been solved:
* Download configuration
* Communication Test in Device
Settings tab
* Update monitoring data (Slave
Diagnostics, clearing error log).
Ensure there are no problems
with the connection between the
Personal Computer and the PLC.
Make sure the Device Settings
are correct.
When
problem
has
removed, disconnect and re-con-
nect. Perform one of the follow-
ing successfully to confirm the
problem has been solved:
* Update monitoring data (Slave
Diagnostics, clearing error log).
* Changing the master state
been