Omron CS1W-AD041-V1 Operation Manual page 90

Sysmac cs/cj series
Table of Contents

Advertisement

Adjusting Offset and Gain
Wiring for Current Input
When using current input, short-circuit the input (+) terminal and the current
mode terminal.
CS1W-AD041-V1/081-V1
Current input
A1
A2
A3
For current input, check that the voltage/
current switch is ON.
CS1W-AD161
+
Current input n
3. Input the voltage or current so that the conversion value is maximized
(0FA0 or 07D0 at a resolution of 4,000). The following table shows the gain
adjustment voltages and currents to be input according to the input signal
range.
Input signal range
0 to 10 V
–10 to 10 V
1 to 5 V
0 to 5 V
4 to 20 mA
4. With the voltage or current having been input so that the conversion value
for the Analog Input Unit is maximized (0FA0 or 07D0), turn bit 04 (the Set
Bit) of CIO word n+1 ON and then OFF again.
C
A
CONT
SHIFT
2
0
#
SET
RESET
While the Gain Bit is ON, the gain value will be saved to the Unit's EE-
PROM when the Set Bit turns ON.
+
Input 1
Input n+
Current mode n
Input n−
Shield
AG
Input range
9.5 to 10.5 V
9.0 to 11.0 V
4.8 to 5.2 V
4.75 to 5.25 V
19.2 to 20.8 mA
(Values in parentheses are for a resolution of 8,000.)
A
B
A
E
0
1
0
200104
200104
200104
Section 2-7
Word (n+8) monitoring value
0ED8 to 1068 (0FB0 to 20D0)
0708 to 0898 (0E10 to 1130)
0ED8 to 1068 (0FB0 to 20D0)
0ED8 to 1068 (0FB0 to 20D0)
0ED8 to 1068 (0FB0 to 20D0)
MON
4
^ OFF
^ ON
^ OFF
67

Hide quick links:

Advertisement

Table of Contents
loading