Omron CS1W-AD041-V1 Operation Manual page 246

Sysmac cs/cj series
Table of Contents

Advertisement

Specifications
Item
Input
Specifications
Functions
Output Specifications
Functions
Other
Functions
Note
Number of analog inputs
Input signal range (See note 3.)
Maximum rated input (for 1 point) (See note
5.)
Input impedance
Resolution
Converted output data
Accuracy
23±2°C
(See note 6.)
0°C to 55°C
A/D conversion time (See note 7.)
Mean value process-
Stores the last "n" data conversions in the buffer, and stores the
ing
the mean value of the conversion values.
Buffer number: n = 2, 4, 8, 16, 32, 64
Peak value holding
Stores the maximum conversion value while the Peak Value Hold
Bit is ON.
Input disconnection
Detects the disconnection and turns ON the Disconnection Detec-
detection (See note
tion Flag.
9.)
Number of analog outputs
Output signal range
(See note 3.)
Output impedance (for 1 point)
Max. output current
Resolution
Set data
Accuracy
23±2°C
(See note 6.)
0°C to 55°C
D/A conversion time (See note 7.)
Output hold function
Outputs the specified output status (CLR, HOLD, or MAX) under
any of the following circumstances.
When the Conversion Enable Bit is OFF. (See note 8.)
In adjustment mode, when a value other than the output number is
output during adjustment.
When there is an output setting error or a fatal error occurs at the
PLC.
When the CPU Unit is on standby.
When the Load is OFF.
Ratio conversion
Stores the results of positive and negative gradient analog inputs
function
calculated for ratio and bias as analog output values.
Positive gradient: Analog output = A × Analog input + B
Negative gradient: Analog output = F – A × Analog input + B
1. Refer to Dimensions on page 359 for details on the Unit's dimensions.
CS1W-MAD44
Voltage input
4
1 to 5 V
0 to 5 V
0 to 10 V
–10 to 10 V
±15 V
1 MΩ min.
4,000 (full scale)
16-bit binary data
±0.2% of full scale
±0.4% of full scale
1.0 ms/point max.
Voltage output
4
1 to 5 V
0 to 5 V
0 to 10 V
–10 to 10 V
0.5 Ω max.
12 mA
4,000 (full scale)
16-bit binary data
±0.3% of full scale
±0.5% of full scale
1.0 ms/point max.
(A = 0 to 99.99, B = 8,000 to 7FFF Hex)
(A = 0 to 99.99, B = 8,000 to 7FFF Hex,
F = output range max. value)
Section 6-1
Current input
4 to 20 mA
(See note 4.)
±30 mA
250 Ω (rated value)
±0.4% of full scale
±0.6% of full scale
223

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents