Step 6 - Make Final Preparations; Start-Up - Carrier 40UV075 Installation, Start-Up And Service Instructions Manual

Unit ventilators
Table of Contents

Advertisement

MOTOR
UNIT SIZE
HP
1
40UV050
/
3
40UV,UH075
1
/
3
1
40UV,UH100
/
3
40UV,UH125
1
/
2
1
40UV,UH150
/
2
40UH200
3
/
4
LEGEND
3-4EH/DX — Direct Expansion Coil Applications with 3 to
4 Elements of Electric Heat
5-6EH
— 5 to 6 Elements of Electric Heat
CW
— Chilled Water Applications
ECM
— Electronically Commutated Motor
ESP
— External Static Pressure
Step 6 — Make Final Preparations
1.
Turn power off (lock out and tag electrical disconnect).
2.
Install thermostats and perform any other final wiring as
applicable.
3.
Clean dirt, dust, and other construction debris from unit
interior. Be sure to check fan wheel and housing.
4.
Rotate fan wheel by hand to be sure it is free and does
not rub on housing.
5.
Be sure drain line is clear and is properly and securely
positioned. Pour water into drain to check operation.
6.
Vent all air from unit coil and related piping. The coil is
provided with a Schrader or screw-type manual air vent
on the return manifold to release air from the coil.
NOTE: This vent is not adequate for removing air from the
building piping system. Customer must provide for venting of
the piping system.
a. Pressurize the building piping system with water.
Vent trapped air at system vents.
b. Schrader type vent: Remove cap. Depress valve at
coil vent until air is expelled from the unit. Release
valve. Re-install cap.
c. Screw type vent: Back out manual setscrew until air
is expelled. Re-tighten setscrew.
d. Automatic type vent: Trapped air will be vented
automatically. Vent releases air slowly, usually drip-
ping water into the drain pan in the process.
Make sure all service valves are open and that motorized control
valves, if supplied, are set for automatic operation.
7.
Check all control valves in the system for proper opera-
tion in accordance with valve manufacturer's instruc-
tions.
8.
Install filter in frame at front of coil. If field-supplied
filters are used, be sure size is correct. See Table 1 for
filter data.
Table 6 — Unit Ventilator Airflow — ECM Airflow
COIL TYPE
Low Position
(0.0 in. wg)
Max
High
CW
499
336
3-4EH/DX
499
419
5-6EH
491
380
CW
747
484
3-4EH/DX
747
644
5-6EH
755
645
CW
997
703
3-4EH/DX
997
853
5-6EH
1016
819
CW
1266
880
3-4EH/DX
1266
1023
5-6EH
1259
1049
CW
1503
1033
3-4EH/DX
1503
1246
5-6EH
1517
1222
ALL
2014
1384
APPROXIMATE AIR DELIVERY (Cfm)
ESP Speed Board Position
Med Position
(0.10 in. wg)
Low
Max
High
Low
248
336
324
346
753
548
432
498
753
609
472
583
746
598
539
505
987
693
543
615
987
850
639
719
1002
851
709
657
1239
905
609
769
1239
1055
758
897
1239
995
888
775
1479
1046
712
956
1479
1216
965
1068
1490
1206
1087
1023
1981
1386
971
NOTES:
1. Factory default is Low Position.
2. Med, High, and Max positions are field settings.
9.
Ensure all panels and filters are installed before checking
fan operation. Turn on unit power. Check fan and motor
operation.
.
IMPORTANT: Do not start up or operate unit without
filter and panels installed. Be sure filter and unit interior
are clean.
Start-up procedures vary depending on time of year (summer or
winter) and building characteristics (new building/old building,
occupied/unoccupied, etc.). All building windows and door
should be closed before starting the unit. Close the unit's outdoor
air dampers. Bathroom and kitchen exhaust fans should be off.
Start-up in the cooling mode requires proper care to avoid con-
densation problems. Condensation forms on surfaces that are
colder than the dew point of the surrounding air. If a unit is start-
ed and is piped with low-temperature chilled water in a hot, hu-
mid atmosphere, condensation will form on many parts of the
unit. In order to avoid excessive condensation, higher tempera-
ture water should initially be used (approximately 65°F to 70°F),
reduce the chilled water flow rate (GPM) and set the fan to high
speed for maximum airflow.
As the building temperature drops, the chilled water temperature
can be gradually reduced until it reaches 50°F. At this point the
outside-air damper can be opened to take in minimum outside
air. When the chilled water temperature is reduced to its design
point, the exhaust fans can be turned on.
Maximum entering water temperature is 180°F, unless name-
plate indicates 200°F.
If unit is marked for 200°F maximum entering water tem-
perature, customer must ensure that water vaporization
does not occur, especially at higher elevations when enter-
ing water temperatures are greater than 190°F.
31
High Position
Max Position
(0.25 in. wg)
(0.45 in. wg)
Max
High
Low
Max
752
530
427
751
752
612
470
751
755
585
554
765
1012
663
483
994
1012
823
626
994
1024
798
787
1024
1235
898
676
1231
1235
1037
765
1231
1226
995
888
1253
1494
1020
770
1486
1494
1209
927
1486
1498
1159
1120
1503
1965
1385
997
1814

START-UP

CAUTION
High
Low
541
386
618
498
610
542
692
480
819
618
820
734
898
627
1010
778
994
919
1075
737
1222
917
1188
1074
1354
993

Advertisement

Table of Contents
loading

Table of Contents