Carrier 40UV075 Installation, Start-Up And Service Instructions Manual page 14

Unit ventilators
Table of Contents

Advertisement

UNIT
HP
40UV,UH150
1
/
5
(at 1500 cfm)
LEGEND
FLA
— Full Load Amps
LAT
— Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA
— Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC
— Permanent Split Capacitor
*Cooling coil must be left-hand coil connections only.
Table 2 — Electric Heater Data for Units with PSC Motor (cont)
NOMINAL
NUMBER OF
V/Ph/Hz
ELEMENTS
3
4
208/1/60
5
6*
3
4
240/1/60
5
6
3
4
277/1/60
5
6
3
4
208/3/60
5
6*
3
4
240/3/60
5
6*
3
4
460/3/60
5
6*
FLA
LAT (F)
45.3
89
59.8
96
74.2
102
88.7
108
52.0
96
68.7
104
85.3
113
44.9
96
59.4
104
73.8
113
27.0
89
41.5
96
52.1
102
52.1
108
30.9
96
47.6
104
59.8
113
59.8
121
15.4
96
23.7
104
29.8
113
29.8
121
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
4. The PSC motor is not available on unit size 200.
14
TOTAL
MCA
MOCP
CAPACITY (kW)
56.7
60
74.7
80
92.8
100
110.8
125
65.0
70
85.8
90
106.7
110
56.2
60
74.2
80
92.3
100
33.8
35
51.9
60
65.1
70
65.1
70
38.6
40
59.5
60
74.8
80
74.8
80
19.2
20
29.6
30
37.3
40
37.3
40
9.0
12.0
15.0
18.0
12.0
16.0
20.0
12.0
16.0
20.0
9.0
12.0
15.0
18.0
12.0
16.0
20.0
24.0
12.0
16.0
20.0
24.0