UNIT
HP
40UV,UH150
1
/
2
(at 1500 cfm)
40UH200
3
/
4
(at 2000 cfm)
LEGEND
ECM
— Electronically Commutated Motor
FLA
— Full Load Amps
LAT
— Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA
— Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
*Cooling coil must be left-hand coil connections only.
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
Table 3 — Electric Heater Data for Units with ECM Motor (cont)
NOMINAL
NUMBER OF
V/Ph/Hz
ELEMENTS
208/1/60
240/1/60
277/1/60
208/3/60
240/3/60
460/3/60
208/1/60
240/1/60
277/1/60
208/3/60
240/3/60
460/3/60
FLA
LAT (F)
3
46.7
89
4
61.1
96
5
75.6
102
6*
90.0
108
3
53.3
96
4
70.0
104
5
86.6
113
6
—
—
3
46.2
96
4
60.7
104
5
75.1
113
6
—
—
3
28.3
89
4
42.8
96
5
53.4
102
6*
53.4
108
3
32.2
96
4
48.9
104
5
61.1
113
6*
61.1
121
3
15.6
96
4
24.0
104
5
30.1
113
6*
30.1
121
3
50.1
84
4
64.6
89
5
79.0
94
6*
93.5
99
3
56.8
89
4
73.5
96
5
90.1
102
6
—
—
3
48.8
89
4
63.3
96
5
77.7
102
6
—
—
3
31.8
84
4
46.3
89
5
56.9
94
6*
56.9
99
3
35.7
89
4
52.4
96
5
64.6
102
6*
64.6
108
3
16.9
89
4
25.2
96
5
31.3
102
6*
31.3
108
17
TOTAL
MCA
MOCP
CAPACITY (kW)
58.3
60
76.4
80
94.4
100
112.5
125
66.6
70
87.5
90
108.3
110
—
—
57.8
60
75.8
80
93.9
100
—
—
35.4
40
53.5
60
66.7
70
66.7
70
40.3
45
61.1
70
76.4
80
76.4
80
19.5
20
30.0
30
37.6
40
37.6
40
62.7
70
80.7
90
98.8
100
116.8
125
71.0
80
91.8
100
112.7
125
—
—
61.0
70
79.1
80
97.1
100
—
—
39.8
40
57.9
60
71.1
80
71.1
80
44.6
45
65.5
70
80.8
90
80.8
90
21.1
25
31.5
35
39.1
40
39.1
40
9.0
12.0
15.0
18.0
12.0
16.0
20.0
—
12.0
16.0
20.0
—
9.0
12.0
15.0
18.0
12.0
16.0
20.0
24.0
12.0
16.0
20.0
24.0
9.0
12.0
15.0
18.0
12.0
16.0
20.0
—
12.0
16.0
20.0
—
9.0
12.0
15.0
18.0
12.0
16.0
20.0
24.0
12.0
16.0
20.0
24.0