Electrical Data; Arq & Grq - Size 024 - Daikin ARQ Installation And Maintenance Manual

Classroom unit ventilators standard series/geothermal series microtech (“j” vintage)
Hide thumbs Also See for ARQ:
Table of Contents

Advertisement

Table 10: Wiring Diagram Legend for
Symbol
Description
A1
Actuator- Outdoor Air
A2
Actuator- Face & Bypass
CP1
Motor Compressor 2-Stage
C1
Compressor Contactor
CAP1
Capacitor Run
CEH1-3
Electric Heat Contactor
CO2
Sensor - Indoor Air CO2
DAT
Sensor - Discharge Air Temperature
DCS
Switch - Unit Power
DF
Dead Front Switch
EH1-6
Heater - Electric
EH10
Heater - Outdoor Drain Pan
F1A/F1B
Fuse - Compressor
F2A/F3C
Fuse - Electric Heat
FA/FB
Fuse– Control, Load
FC/FD
Fuse– Control, Transformer
FMI
Motor - Room Fan
FMO
Motor Outdoor Air
Notes:
1.
All electrical installation must be in accordance with national and local electrical codes and job wiring schematic.
2.
External wiring options - see IM for the different configured options, wiring to be minimum 18 gauge, 90°C.
3.
EC motors are factory programmed for specified air flow. Contact Daikin Applied for replacement.
4.
Cap extra wire. Switch wire 42A to red wire for 208V operation.
5.
Switch wire 509 to terminal 2 for 208V operation.
6.
Devices in legend may or may not be on unit.

Electrical Data

ARQ & GRQ – Size 024
Voltage Range
Volt/Hz/Phase
Min.
Max.
208/60/1
197
228
230/60/1
207
253
208/60/3
197
228
230/60/3
207
253
460/60/3
414
506
1 Electric Heat Options are without Compressor and Outdoor Fan.
IM 1083-3
Figure 43 on page 26 and Figure 44 on page 27
Symbol
Description
HP
High Pressure Switch
ICT
Sensor - Indoor DX Coil Temperature
IH
Sensor - Indoor Humidity
MCB
Main Control Board
NTWK
Network Connection
OAT
Sensor - Outdoor Air Temperature
OCT
Sensor - Outdoor DX Coil Temperature
OH
Sensor - Outdoor Humidity
OH1
Thermostat - Overheat
OH2
Thermostat - Overheat
OHM
E.H. Man Reset - Overheat Stat
PL1
LED Occupancy / Fault Status
R1-R3
Relay Electric Heat (Backup)
R10-R12
Relay – Electric Heat
R4H
Relay – Fan High Speed
R4M
Relay– Fan Medium Speed
R4L
Relay– Fan Low Speed
Compressor
Room Fan
FLA
RLA
LRA
2.7
11.7
58.3
2.7
11.7
58.3
2.7
11.7
58.3
2.7
11.7
58.3
2.7
11.7
58.3
2.7
11.7
58.3
2.7
6.5
55.4
2.7
6.5
55.4
2.7
6.5
55.4
2.7
6.5
55.4
2.7
6.5
55.4
2.7
6.5
55.4
2.7
3.5
28.0
2.7
3.5
28.0
2.7
3.5
28.0
Symbol
R32
R28
RV
RAT
T6
TB1
TB2
TB3
TBE
TR1
TR3
TR4
TR5
V1
V2
VH
VC
Heating Option
Heat Type
None
Low (3 elem.)
Elec. Heat 1
High (6 elem.)
None
Low (3 elem.)
Elec. Heat 1
High (6 elem.)
None
Low (3 elem.)
Elec. Heat 1
High (6 elem.)
None
Low (3 elem.)
Elec. Heat 1
High (6 elem.)
None
Low (3 elem.)
Elec. Heat 1
High (6 elem.)
28
Description
Relay - Drain Pan Heater
Relay - Outdoor Motor Air
Reversing Valve
Sensor - Room Air Temperature
Thermostat - Freeze Stat
Terminal Block - 24VAC+
Terminal Block – 24VAC Gnd
(A, B) Terminal Block – Main Power
Terminal Block - Electric Heat
Transformer - Motor Speed
Transformer - 208 / 230V-24V, 75VA
Transformer - 460V–230V
Transformer - 208 / 230V-24V
Valve - Heat EOC (Accessory)
Valve - Cool EOC (Accessory)
Valve - Heat (Accessory)
Valve - Cool (Accessory)
Power Supply
Rated
Heater
Heater
MCA
Kw
Amps
17.3
8.0
38.5
65.4
16.0
76.9
113.5
17.3
7.3
33.3
59.0
14.7
66.7
100.7
10.8
8.0
22.2
38.6
16.0
44.4
66.3
10.8
7.3
19.2
34.9
14.7
38.5
58.9
7.1
7.3
9.6
19.1
14.7
19.2
31.1
www.DaikinApplied.com
Maximum
Fuse
25
70
125
25
60
110
15
40
70
15
35
60
15
20
35