DPSA Gas Furnace Capacity Data

Table 29: DPSA Natural Gas Furnace Capacity Table
Heat Size
Efficiency
Fuel
MBH
(%)
(KW)
200
81
(58.6)
400
81
(117.2)
600 (175.8)
81
Natural Gas
800
81
(234.5)
1125
81
(329.7)
www.DaikinApplied.com
Supply
Max Out
Press .
Temp
min-max
Control
°F
IN WC
(°C)
(kPa)
2 Stage
7-14
120
(1.7-3.5)
(49)
5:1 Modulation
2 Stage
7-14
120
5:1 Modulation
(1.7-3.5)
(49)
10:1 Modulation
2 Stage
4 Stage
7-14
120
(1.7-3.5)
(49)
5:1 Modulation
10:1 Modulation
10:1 Modulation
7-14
120
(1.7-3.5)
(49)
20:1 Modulation
10:1 Modulation
7-14
120
(1.7-3.5)
(49)
20:1 Modulation
127
Rated Input
Rated
Temp Rise
Low/ High
Output
MBH
MBH
(°C)
(KW)
(KW)
110/200
(32.2/58.6)
162
(47.5)
(14)
40/200
(11.7/58.6)
220/400
(64.5/117.2)
80/400
324
(23.4/117.2)
(95)
(28)
40/400
(11.7/117.2)
(28)
300/600
486
(87.9/175.8)
(142.4)
(39)
(28)
165/600
486
(48.4/175.8)
(142.4)
(39)
(28)
120/600
486
(35.2/175.8)
(142.4)
(39)
(28)
60/600
486
(17.6/175.8)
(142.4)
(39)
(33)
80/800
648
(23.4/234.5)
(189.9)
100
(56)
(33)
40/800
648
(11.7/234.50
(189.9)
100
(56)
(33)
112/1125
911
(32.8/329.7)
(267.1)
100
(56)
(33)
56/1125
911
(16.4/329.7)
(267.1)
100
(56)
IM 1287-4 • REBEL APPLIED ROOFTOP
Unit Maintenance
Min Airflow
°F
CFM
(M3/HR)
25
5972
(10147)
50
5972
(10147)
50
8959
(15221)
70
6399
(10872)
50
8959
(15221)
70
6399
(10872)
50
8959
(15221)
70
6399
(10872)
50
8959
(15221)
70
6399
(10872)
60
9954
(16912)
5972
(10147)
60
9954
(16912)
5972
(10147)
60
13998
(23782)
8399
(14269)
60
13998
(23782)
8399
(14269)

Hide quick links: