Table 12. Manual output test sequence for face-and-bypass configurations (two-position isolation valves only)
Step
Result
BOP1
1
Begins test
Off
Off
1
mode
2
2
Fan high
On/High
Off
3
Fan
Off
1) On/Med
3
medium
2) Off
4
4
Fan low
Off
Off
5
Main open,
On/High
Off
DX on
6
Main close,
On/High
Off
DX off, aux
open
7
Aux open,
On/High
1) Off
EH1 on,
2) On
exhaust
5
fan
8
Aux close,
On/High
Off
damper
open
9
Outdoor air
On/High
Off
damper
close
10
Generic/
On/High
Off
baseboard
heat
6
energized
5
11: Exit
1
The controller turns off all fan and electric heat outputs and drives all dampers and valves closed.
2
The controller attempts to clear all diagnostics.
3
If configured for a 3-speed fan, the medium fan speed output will energize at step 3. If configured for a 2-speed fan, the fan remains on high speed at step 3.
4
If configured for a 3-speed fan, the medium fan speed output energizes at step 4. If configured for a 2-speed fan, the low fan speed output energizes at step 4. If configured
for a 1-speed fan, the fan remains on high speed at step 4.
5
If the unit is configured for a 1- or 2-speed fan, the exhaust fan output energizes on step 7. The exhaust fan output is shared with medium fan speed.
6
After step 10, the manual output test performs an exit, which initiates a reset to restore the controller to normal operation.
BOP2
BOP3
BOP4
Off
Off
Off
Off
Off
Off
On/Low
Off
Off
On/Open
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
BOP5
BOP6
BOP7
Off
Off
On/Close
On/Open
Off
Off
On/Open
Off
Off
On/Open
Off
Off
On/Open
Off
Off
On/Open
On/Open
Off
On/Open
On/Open
Off
Off
Off
On/Close
Off
Off
On/Close
Off
Off
On/Close
BOP8
BOP9
BOP10
Off
On/Close
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On/Open
Off
Off
Off
On/Close
Off
Off
Off
On