Trane Tracer ZN521 Installation And Operation Manual page 22

Zone controller
Hide thumbs Also See for Tracer ZN521:
Table of Contents

Advertisement

Input/output functions and wiring for typical applications
Figure 9. Two-pipe hydronic heating/cooling unit with auto changeover
Condensate overflow (closed=normal)*
Low-coil-temperature detection
(closed=normal)*
H
24 Vac
N
22
Fan status (closed=on)
Occupancy (open=occupied)*
Entering water
LonTalk
temperature
Discharge air
temperature
24 V
Fan, high speed
24 V
Exhaust (or fan, medium speed)
24 V
Fan, low speed
*
AI4 input: See
Figures
Step 5
and
Step 6
on
p. 18
for wiring
options
Outdoor air or
generic temperature
* All binary inputs are configurable.
Connect 24 V to an AC POWER (24V) terminal.
24 V
Heating/cooling changeover valve
24 V
Electric heat, stage 1 (optional)
24 V
Electric heat, stage 2 (optional)
24 V
Outdoor air damper actuator
24 V
Generic/baseboard heat
LonTalk
in
out
CNT-SVX07D-EN