Trane Tracer ZN521 Installation And Operation Manual page 25

Zone controller
Hide thumbs Also See for Tracer ZN521:
Table of Contents

Advertisement

Figure 12. Two-pipe heating unit with DX cooling
Condensate overflow (closed=normal)*
Low-coil-temperature detection
(closed=normal)*
H
24 Vac
N
GND
On
Cancel
CNT-SVX07D-EN
Input/output functions and wiring for typical applications
Fan status (closed=on)*
Occupancy (open=occupied)*
24V
24V
24V
BI1
BI2
AC POWER
BINARY INPUTS
ZONE SENSOR
SERVICE
PIN
LED
ZN GND
SET
FAN GND
1
2
3
4
Entering water
5
LonTalk
temperature
6
Discharge air
temperature
24 V
Fan, high speed
24 V
Exhaust (or fan, medium speed)
24 V
Fan, low speed
BI3
BI4
1
2
3
4
BINARY OUTPUTS
ANALOG INPUTS
AI1
AI2
AI3
+20
AI4
AI4 input: See
Figures
Step 5
and
Step 6
p. 18
for wiring
options
Outdoor air or generic temperature
* All binary inputs are configurable.
Connect 24 V to an AC POWER (24V) terminal.
24 V
DX cooling
24 V
Heating valve
24 V
Outdoor air damper actuator
24 V
Generic/baseboard heat
5
6
7
8
9
10
STATUS
LED
COMM5
COMM5
GND
A
B
A
B
LED
on
LonTalk
in
out
25

Advertisement

Table of Contents
loading

Table of Contents