Functions Of Terminals For Main Circuit - Panasonic AMK3000P22 Installation Manual

Mk300 series. 1-phase 200v(0.2kw-2.2kw), 3-phase 400v(0.75kw-15kw)
Table of Contents

Advertisement

Functions of terminals for main circuit

Terminal No.
R/L1, S/L2, T/L3
L1, L2
U, V, W
P/DB+, DB–
N–
2 个
Terminal name
P o w e r s u p p l y f o r
main circuit
Inverter output
B r a k i n g r e s i s t o r
connection
Internal DC voltage
(negative)
Ground
Descriptions of terminal function
Connects the electricity for industrial use.
For 1-phase 200V type, connect to
terminal L1 and L2.
Connects to 3-phase motor.
Connects to braking resistor.
Negative terminal of internal DC voltage.
Ground terminal.
For 1-phase 200V type: Grounding
resistance of 100Ω or less
3-phase 400V: ground resistance 10Ω or
less Ground the neutral of power supply.