Precautions On Using Regenerative Braking; Connected Device, Wire Size And Tightening Torque - Panasonic AMK3000P22 Installation Manual

Mk300 series. 1-phase 200v(0.2kw-2.2kw), 3-phase 400v(0.75kw-15kw)
Table of Contents

Advertisement

Precautions on using regenerative braking

· When using regenerative braking, set the parameter P026 to "0". Since the factory
setting is "1", the braking will not work.

Connected device, wire size and tightening torque

• 1-Phase 200V
Rated
current
Inverter
of circuit
capacity
breaker
(MCCB)
for wiring
0.2kW
10A
0.4kW
15A
0.75kW
20A
1.5kW
30A
2.2kW
40A
•3-phase 400V
Rated
current
Inverter
of circuit
capacity
breaker
(MCCB)
for wiring
0.75kW
10A
1.5kW
15A
2.2kW
20A
3.7kW
30A
5.5kW
50A
7.5kW
50A
11kW
70A
15kW
80A
*1) The above data is only for the reference of the condition with braking torque of
100%, maximum time of 5s and maximum braking duty factor of 5%.
Wire size
L1, L2
Ground
U, V, W
wire
2
2
2mm
2mm
(AWG14)
(AWG14)
2
2
3.5mm
3.5mm
(AWG12)
(AWG12)
Wire size
L1, L2
Ground
U, V, W
wire
2
2
2mm
2mm
(AWG14)
(AWG14)
2
3.5mm
(AWG12)
2
3.5mm
2
(AWG12)
3.5mm
(AWG12)
2
2
8mm
(AWG8) 8mm
(AWG8)
2
2
14mm
(AWG6) 14mm
(AWG6)
Screw
Tightening
size
torque
M3.5
1.0 N · m
(Ground :
(Ground :1.2
M4)
N · m)
1.2 N ·
M4
m
Screw
Tightening
size
torque
M4
1.2 N · m
M5
2.0 N · m
Braking resistor *1
Allowable
braking
Resistance
duty factor
120Ω
5%
80Ω
Braking resistor *1
Allowable
braking
Resistance
duty
factor
5%
470Ω
5%
470Ω
5%
320Ω
5%
190Ω
5%
117Ω
5%
95Ω
5%
63Ω
5%
63Ω
Allowable
continuous
power
80W
120W
Allowable
continuous
power
80W
80W
120W
220W
340W
440W
660W
660W
16