Panasonic AMK3000P22 Installation Manual page 38

Mk300 series. 1-phase 200v(0.2kw-2.2kw), 3-phase 400v(0.75kw-15kw)
Table of Contents

Advertisement

Item
Regenerative
braking
torque
DC injection
braking
Analog
output
Open-
collector
output
Relay output
Operation/
Control
status
Details of
abnormality
Current limit Current limit can be set within 1% to 200% of rated output current.
Trip (stop)
Stall
prevention
function
Ambient
temperature
and humidity
Storage
temperature
and humidity
Vibration
Altitude
Location
IP protection
Cooling method
Note 1) It is -10℃ to +40℃ when multiple inverters are installed side-by-side.
37
· 200V 0.2kW : 100% or higher 0.4kW : 80% or higher
    0.75kW to 2.2kW : 20% or higher
· 400V 0.75kW to 15kW : 20% or higher
Operate at the frequency below stop frequency
· Braking torque level: 0 to 100
· Braking time: adjustable from 0.1s to 120s
Output specification: 0V to 10V DC (max. 1 mA)
Output function: output frequency and output current proportion
(switchable)
Output specification : max. rating 50V DC/50mA
Output functions : operation signal, arrival signal. overload alarm,
frequency detection, abnormal reverse run signal
alarm, current detection, timer OFF signal,
output frequency/current proportion PWM signal
output frequency/current proportion pulse train signal
Output specification : 1c contact
(Contact capacity: 230V AC 0.25A resistive load
30V DC 1A resistive load)
Output functions : operation signal, arrival signal. overload alarm,
frequency detection, abnormal reverse run
signal alarm, current detection, timer OFF signal
(switchable)
Output frequency, linear speed display (switchable), rotation direction
Ouput voltage, internal DC voltage, set frequency, communication
station No., operation times of timer, alarm type, control circuit
terminal status (I/O signal), operation status, PID (setting value,
mesured value and output value), progress of automatic tuning,
accumulative operating time, accumulative operating time of fan
Specific symbol is indicated when the protection function is
activated (the latest four abnormalities are stored.)
Instantaneous overcurrent (SC1-6), abnormal temperature
(OH) overcurrent(OC1-3),overload · electronic thermal relay
(OL), undervoltage (LU), overvoltage (OU1-3), cooling fan fault
(FAn,FAn2), external fault(AU), operation fault(OP), CPU error
(CPU,ErrC)
Overcurrent and overvoltage stall prevention
-10℃ to + 50℃ (Note 1) (without freezing) and below 90%RH
(without condensation)
-25℃ to +65℃ and below 95%RH
2
5.9m/s
(0.6 G) max.
1000m max.
Indoor areas free of corrosive gases, flammable gases, oil mist or dust
IP20 cabinet-mounted
0.75kW or lower: natural cooling; 1.5kW to 15kW: air-cooling
Specifications