Current status of the ballasts though, is not updated automatically – you need to press
button Refresh to obtain it at the moment you want to check it.
Remember that DALI ballasts locally keep their configuration parameters and short address
in their own permanent storage memory, as well as does the IntesisBox itself – in
particular, this means that if you physically disconnect a ballast from the DALI bus
controlled by the IntesisBox, the ballast will still keep its short address and configuration
values.

3.4.4 Ballast configuration values

The configuration parameters for the ballasts are accessible by clicking on tab DALI Config
in IntesisBox Configuration window.
Figure 13 - DALI Ballast Configuration parameters window
At first, you will get a list of ballasts 0 to 63 (ordered by their short address) and an
indication if they are Online or Offline. Press button Read from DALI to obtain current
configuration of all ballasts present in database.
Figure above shows the configuration grid as it appears when first accessing this tab, figure
below shows how it looks like after having read ballast configuration parameters from the
bus.
Figure 14 - Ballast configuration parameters have been read from bus
2
File: IBOX-BAC-DALI User Manual eng r1.pdf
© Intesis Software S.L. - All rights reserved
IntesisBox is a registered trademark of Intesis Software SL
User's Manual eng r0
URL
http://www.intesis.com
email
info@intesis.com
tel
+34 938047134
20 / 26

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IBOX-BAC-DALI and is the answer not in the manual?

Questions and answers

Table of Contents