4.3.2 Wire types and ratings
All cables must comply with local and national standards in terms of section and ambient
Use cables with minimum heat resistance +70°C (158°F); to ensure compliance with UL
Cables must never enter into contact with the motor body, the pump and the piping.
The wires connected to the power supply terminals and the fault signal relay (NO, C) must be
Table 4: Electric connection cables
e-SM Drive models
103, 105, 107, 111,
303, 305, 307, 311,
Control cables
External volt free contacts must be suitable for switching < 10 VDC.
NOTICE:
Install the control cables separate from the power supply cables and the fault signal relay
If the control cables are installed in parallel with the power supply cable or the fault signal
Do not intersect the power supply cables; should this be necessary, a 90°intersection angle is
Table 5: Recommended control cables
e-SM Drive control cables
temperature
(Underwriters Laboratories) regulations, all power supply connections must be completed
using the following types of copper cables with minimum resistance +75°C: THW, THWN
separated from the others by means of reinforced insulation.
Power supply input cable + PE
Wire numbers
x Max. copper
section
3 x 1.5 mm
115
3 x 0.0023 sq.in
4 x 1.5 mm
315, 322
4 x 0.0023 sq.in
cable
relay, the distance between the cables must exceed 200 mm
permitted.
All I/O conductors
Wire numbers
x Max. AWG
2
3 x 15 AWG
2
4 x 15 AWG
Wires number
x Max. copper Section
2
0.75-1.5 mm
0.00012-0.0023 sq.in
en – Original instructions
Tightening torque
Mains and motor
cable terminals
Spring connectors
0.8 Nm
7.1 lb-in
AWG
Tightening torque
18-16 AWG
Earth Conductor
Spring connectors
3 Nm
26.6 lb-in
0.6 Nm
5.4 lb-in
21