Settings Parameters; Drive Configuration Parameters - Lowara e-SVE Installation, Operation And Maintenance Manual

Smart pump range
Table of Contents

Advertisement

en – Original instructions
P10
P11
P12
P13
P14
P15
P16
P17

6.5.2 Settings Parameters

No.
P20
P21
P22
P23

6.5.3 Drive Configuration Parameters

No.
P25
*
Depending on the type of pump used
32
2nd error
3rd error
4th error
Power Module
Temperature
Inverter Current
Inverter Voltage
Motor Speed
Software version
Parameter
Description
Password
The user can enter here the system password, which gives access to all system parameters:
entering [0-
this value is compared with the one stored in P22.
999]
When a correct password is entered, the system remains unlocked for 10 minutes.
Jog mode
It deactivates the internal controller of the unit and forces the actual Control Mode (ACT):
*
[MIN-MAX
]
the motor starts and the value of P21 becomes the temporary ACT setpoint. It can be
changed by just entering a new value on P21 without confirming it; otherwise, it causes
immediate exit from temporary control.
System
This is the system password, and must be the same as the password entered in P20.
password [1-
Default: 66.
999]
Lock Function
By using this function, the user can lock or unlock parameter setting in the main menu.
[OFF, ON]
When ON, enter the P20 password to change the parameters.
Default: ON.
Parameter
Unit of
measurement
Control mode
[ACT, HCS, MSE,
MSY]
Saves the penultimate error in chronological occurred.
Other characteristics: like P09.
Saves the third from the last error in chronological occurred.
Other characteristics: like P09.
Saves the fourth from the last error in chronological occurred.
Other characteristics: like P09.
°C
Temperature of the power module.
A
This parameter shows the actual current supplied by the frequency
converter.
V
This parameter shows the actual estimated input voltage of the
frequency converter.
rpmx10
This parameter shows the actual motor rotational speed.
This parameter shows the Control Board software version.
Description
This parameter sets the Control Mode (default value: HCS)
ACT: Actuator mode.
A single pump maintains a fixed speed at any flow rate. ACT will
always try to minimize the difference between the speed setpoint and
the actual rotational speed of the motor.
If a 0-10V signal is supplied to terminals 7 and 8, the pump
automatically switches to ACT mode, following the external signal, as
shown in figure 17.
If the external signal is missing, the pump remains in ACT mode, using
the value set as setpoint using the display.
HCS: Hydrovar® Controller mode for Single pump.
The pump maintains a constant pressure at any flow rate: the
Hydrovar® algorithm, based on the set of parameters from P26 to P37
(see Par. 6.5.3), is implemented.
HCS mode must be set in conjunction with the use of an absolute
reading pressure sensor installed in the hydraulic circuit, which