<2> Use a gauge that is within the applicable range for gauges for the drive when terminals P and B are connected to
the following drives. Junction terminals are needed to connect to the drives if using a gauge that is smaller than the
applicable range for gauges for the drives. Contact Yaskawa or your nearest sales representative when selecting
and connecting junction terminals.
Drive models: CIPR-GA702110, 2138, 4103, CIPR-CH702088, 2115, 4091, CIPR-CR702088, 2115, 4091
<3> Junction terminals are needed to connect to the drives when terminals P and B are connected to the following
drives. Contact Yaskawa or your nearest sales representative when selecting and connecting junction terminals.
Drive models: CIPR-GA704140, 4168, CIPR-CH704112, 4150, CIPR-CR704112, 4150
Note: Use the recommended gauges to connect the CDBR Braking Unit to the following drives and to
comply with an IP20 enclosure. The wiring cover for the +3 and - drive terminal must be cut out.
Refer to the drive manual for details.
Drive models: CIPR-GA702257 to 2415, 4208 to 4675, CIPR-CH702215 to 2415, 4180 to
4605, CIPR-CR702215 to 2415, 4180 to 4605
Replacing Previous Version CDBR Braking Unit Models
The terminal size and location are different on CDBR-X, CDBR-XB, or CDBR-XC model
CDBR Braking Units.
Refer to
Table 11
to ensure proper wiring when replacing an older model CDBR Braking
Unit.
Table 11 CDBR Main Circuit Terminal Cross-Reference Chart
CDBR-D
-
+
B1
B2
Using CDBR Braking Units in Parallel
Install multiple CDBR Braking Units in a master/slave configuration with a single CDBR
Braking Unit as the master as shown in
NOTICE: Perform all wiring and installation as instructed in
damage the drive and the CDBR braking unit.
• Set the Master/Slave Selection Switch (S2) to "Master (OUT)" on one CDBR Braking
Unit only. Set all other CDBR Braking Units to "Slave (IN)". Refer to
Selection Switch (S2) on page 57
• Select the appropriate CDBR Braking Unit wire types and gauges from
• Use shielded twisted-pair cables and keep the wiring distance between the OUT1-IN1 and
OUT2-IN2 terminals of the CDBR Braking Unit shorter than 1 meter (3.28 ft).
YASKAWA ELECTRIC TOBP C720600 01E YASKAWA AC Drive Option CDBR-D, LKEB- Installation Manual
CDBR-B, CDBR-C
-
+
+
0
-
0
Figure
21.
Figure
for details.
6 Electrical Installation
CDBR-
N
P
P
B
21. Failure to follow specifications may
Master/Slave
Table
0
10.
53