6 Electrical Installation
Table 9 CDBR Braking Unit Control Circuit Terminals
Terminal
Terminal No.
Block
IN1
IN2
OUT1
TB1
OUT2
SC
<1>
SB
<1>
MA
MB
MC
TB2
EA
EB
EC
<1> Digital Input-SB, SC. Powered by internal 24 Vdc LVLC source. When using an external power supply, it shall be
UL Listed Class 2 power source only or equivalent.
50
YASKAWA ELECTRIC TOBP C720600 01E YASKAWA AC Drive Option CDBR-D, LKEB- Installation Manual
Terminal Name
Slave Input
Master Output
Enable Input
Fault Contact Output
(N.O.)
Fault Contact Output
(N.C.)
Fault Contact Output
Common
CDBR Transistor
Short-Circuit Detection
Output (N.O.)
CDBR Transistor
Short-Circuit Detection
Output (N.C.)
CDBR Transistor
Short-Circuit Detection
Output Common
Specification
Input the signal when using CDBR braking units in
parallel.
Output the signal when using CDBR braking units in
parallel.
Enable/Disable contact input to disable the CDBR and
activate MA-MB-MC fault contact output.
Output signal when a fault occurs or when SB-SC is closed
(default) (example: CDBR braking unit overheating, LKEB
braking resistor unit short-circuit detection, external fault).
Wiring sequence should shut off power to the drive when
the signal is output.
Relay output
250 Vac, max.1 A
30 Vdc, max.1 A
min.5 Vdc, 10 mA
Output signal when braking unit fault is detected.
If needed, wiring sequence should shut off power to the
drive when the signal is output.
Relay output
250 Vac, max.1 A
30 Vdc, max.1 A
min.5 Vdc, 10 mA