Chapter 5
1756-OF8I Isolated Analog Output Module
IMPORTANT: Remember the following:
• If separate power sources are used, do
not exceed the specific isolation
voltage. For more information on
module specifications, see the 1756
ControlLogix I/O Specifications
Technical Data, publication
1756-TD002.
• Place additional devices anywhere in
the loop.
Drive Different Loads with
the 1756-OF8I Module
96
Figure 30 - 1756-OF8I Module Wiring Diagram - Voltage Output Type
2
1
OUT_0/V
4
3
OUT_0/I
6
5
RTN_0
8
7
Not used
0 1
9
OUT_2/V
12
11
OUT_2/I
4 1
3 1
RTN_2
6 1
5 1
Not used
OUT_4/V
8 1
7 1
OUT_4/I
0 2
9 1
2 2
1 2
RTN_4
Not used
4 2
3 2
6 2
5 2
OUT_6/V
OUT_6/I
8 2
7 2
0 3
9 2
RTN_6
2 3
1 3
Not used
Not used
34
33
6 3
5 3
Not used
When the 1756-OF8I module operates with a Current output load, each channel
automatically adjusts its output power for 0...1000 ohm loads. The module's 24V
backplane current requirements vary based on load.
For more information the module's 24V current requirements, see the 1756
ControlLogix® I/O Specifications Technical Data, publication 1756-TD002.
Rockwell Automation Publication 1756-UM540E-EN-P - December 2017
+
OUT_1/V
>1000 Ω User
Analog Output
OUT_1/I
Device
RTN_1
Not used
OUT_3/V
OUT_3/I
RTN_3
Not used
OUT_5/V
OUT_5/I
RTN_5
Not used
OUT_7/V
OUT_7/I
RTN_7
Not used