Appendix A
Analog I/O Module Tag Definitions
Table 29 - 1756-IF8I Module - Input Tags (continued)
Tag Name
Ch[x].HAlarm
Ch[x].HHAlarm
Ch[x].RateAlarm
Ch[x].CalibrationFault
Ch[x].Calibrating
Ch[x].CalGoodLowRef
Ch[x].CalBadLowRef
Ch[x].CalGoodHighRef
Ch[x].CalBadHighRef
Ch[x].CalSuccessful
Ch[x].RateOfChange
186
Data Type
Definition
BOOL
Triggered when the I.Ch[x].Data tag value is greater than
the C.Ch[x].HAlarmLimit tag value.
If latched, this tag remains set until unlatched or if the
I.Ch[x].Data tag value is within Deadband.
BOOL
Triggered when the I.Ch[x].Data tag value is greater than
the C.Ch[x].HHAlarmLimit tag value.
If latched, this tag remains set until unlatched or if the
I.Ch[x].Data tag value is within Deadband.
BOOL
Triggered when the absolute change between
consecutive channel samples exceeds the
C.Ch[x].RateAlarmLimit tag value.
If latched, this tag remains set until it is unlatched.
BOOL
Indicates that the channel is not calibrated or the last
attempted calibration for this channel failed.
If the last calibration failed, this tag is cleared, that is, set
to 0, when power is cycled to the module.
BOOL
Indicates the channel is currently being calibrated.
BOOL
Indicates that a valid Low Reference signal has been
sampled on this channel.
BOOL
Indicates that an invalid Low Reference signal has been
sampled on this channel.
You must correct this condition to successfully calibrate
the module.
If calibration is aborted with an invalid Low Reference
signal, the I.Ch[x].CalibrationFault tag is set for this
channel until a successful calibration is performed or a
reset or RIUP occurs.
BOOL
Indicates that a valid High Reference signal has been
sampled on this channel.
BOOL
Indicates that an invalid High Reference signal has been
sampled on this channel.
You must correct this condition to successfully calibrate
the module.
If calibration is aborted with an invalid High Reference
signal, the I.Ch[x].CalibrationFault tag is set for this
channel until a successful calibration is performed.
BOOL
Indicates calibration on this channel is complete and the
Calibrating state has been exited.
This tag remains set after valid calibration for 1000
samples.
REAL
Change in channel data since last sample in
Engineering Units/Second.
Rockwell Automation Publication 1756-UM540E-EN-P - December 2017
Valid Values
• 0 = Alarm is not triggered
• 1 = Alarm is set
• 0 = Alarm is not triggered
• 1 = Alarm is triggered
• 0 = Alarm is not triggered
• 1 = Alarm is triggered
• 0 = Calibration did not fail
• 1 = Calibration failure
• 0 = Channel is not being
calibrated
• 1 = Channel is being calibrated
• 0 = Valid Low Reference signal
has not been sampled on this
channel
• 1 = Valid Low Reference signal
has been sampled on this
channel
• 0 = Invalid Low Reference signal
has not been sampled on this
channel
• 1 = Invalid Low Reference signal
has been sampled on this
channel
• 0 = Valid High Reference signal
has not been sampled on this
channel
• 1 = Valid High Reference signal
has been sampled on this
channel
• 0 = Invalid High Reference
signal has not been sampled on
this channel
• 1 = Invalid High Reference
signal has been sampled on this
channel
• 0 = Calibration was not
successful
• 1 = Calibration was successful
and calibrating state has been
exited.
Value representing the rate
of change
0.0 = default (This value indicates
no change occurred since sample.)