Allen-Bradley 1756-IF8I User Manual page 187

High resolution analog i/o modules
Hide thumbs Also See for 1756-IF8I:
Table of Contents

Advertisement

Table 29 - 1756-IF8I Module - Input Tags (continued)
Tag Name
Ch[x].Data
Timestamp
RollingTimestamp
Data Type
Definition
REAL
Channel data in scaled Engineering Units.
DINT[2]
64-bit timestamp indicating when all 8 channels were
last sampled in terms of CIPSync time.
DINT
16-bit timestamp that 'rolls' from 0...32,767 ms.
Compatible with existing PID/PIDE instructions to
automatically calculate sample deltas. With this module,
this PID/PIDE instruction uses the RPI because there is no
RTS available.
For more information on the Rolling Timestamp, see
page
23.
Rockwell Automation Publication 1756-UM540E-EN-P - December 2017
Analog I/O Module Tag Definitions
Valid Values
Any positive or negative value.
Determined by how you set the
scaling parameters on the channel.
For more information, see
on page
32.
CIPSync Timestamp data
0...32,767 ms;
where 1 ms = 1 count
Appendix A
Scaling
187