Raid And Expansion Chassis Site Wiring And Ac Power Requirements - Quantum QXS-312 Site Planning Manual

Qxs-3/4/6 series hybrid storage
Hide thumbs Also See for QXS-312:
Table of Contents

Advertisement

RAID and Expansion Chassis Site Wiring and AC Power Requirements

Table 26
provides the RAID chassis AC power requirements required for all installations using AC
power supplies in the QXS 12, 24, 48, and 56-drive systems.
Table 26 QXS RAID Chassis 12, 24, 48, and 56-Drive Power Requirements (AC Input)
Measurement (AC)
Rating for 12-Drive
Chassis
Input power
100 to 240VAC,
requirements
50/60Hz, 7.2A
Maximum input
475W maximum
power
continuous
Heat dissipation
1622 BTUs/hour
Power Supply
Bronze Rated-high
efficiency
82% @ 20% load
86% @ 80% load
85% @ 100% load
Table 27
provides the expansion chassis AC power requirements required for all installations using AC
power supplies in the QXS 12, 24, 48, and 56-drive systems.
Table 27 QXS Expansion Chassis 12, 24, 48, and 56-Drive Power Requirements (AC Input)
Measurement (AC)
Rating for 12-Drive
Chassis
Input power
100 to 240VAC,
requirements
50/60Hz
Maximum input
436W maximum
power
continuous
Heat dissipation
1488 BTUs/hour
Power Supply
Bronze Rated-high
efficiency
82% @ 20% load
86% @ 80% load
85% @ 100% load
Additional requirements include:
• All AC mains and supply conductors to power distribution boxes for the rack-mounted system
must be enclosed in a metal conduit or raceway when specified by local, national, or other
applicable government codes and regulations.
• Ensure that the voltage and frequency of your power source match the voltage and frequency
inscribed on the equipment's electrical rating label.
40
QXS Site Planning Guide
Rating for 24-Drive
Rating for 48-Drive
Chassis
Chassis
100 to 240VAC,
100 to 240VAC,
50/60Hz, 7.2A
50/60Hz
475W maximum
640W maximum
continuous
continuous
1622 BTUs/hour
2245 BTUs/hour
Bronze Rated-high
Gold Rated-high
efficiency
efficiency
82% @ 20% load
75% @ 10% load
86% @ 80% load
88% @ 20% load
85% @ 100% load
92% @ 50% load
88% @ 100% load
Rating for 24-Drive
Rating for 48-Drive
Chassis
Chassis
100 to 240VAC,
100 to 240VAC,
50/60Hz
50/60Hz
436W maximum
640W maximum
continuous
continuous
1488 BTUs/hour
2245 BTUs/hour
Bronze Rated-high
Gold Rated-high
efficiency
efficiency
82% @ 20% load
75% @ 10% load
86% @ 80% load
88% @ 20% load
85% @ 100% load
92% @ 50% load
88% @ 100% load
Rating for 56-Drive
Chassis
200 to 240VAC,
50/60Hz
958W maximum
continuous
3271 BTUs/hour
Gold Rated-very
high efficiency
82% @ 10% load
90% @ 20% load
94% @ 50% load
91% @ 100% load
Rating for 56-Drive
Chassis
200-240VAC
50/60Hz;6-5A
(1200W)
1200W maximum
continuous
4095 BTUs/hour
Platinum Rated-very
high efficiency
82% @ 10% load
90% @ 20% load
94% @ 50% load
91% @ 100% load

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qxs-456Qxs-448Qxs-412Qxs-324Qxs-424Qxs-648 ... Show all

Table of Contents