MTU 12V2000Gx6 series Operating Instructions Manual page 96

Table of Contents

Advertisement

347 – AL Open Load Cylinder A7
Yellow alarm; warning
Cause
Open circuit in cylinder A7
injector wiring. Result: Misfiring.
348 – AL Open Load Cylinder A8
Yellow alarm; warning
Cause
Open circuit in cylinder A8
injector wiring. Result: Misfiring.
349 – AL Open Load Cylinder A9
Yellow alarm; warning
Cause
Open circuit in cylinder A9
injector wiring. Result: Misfiring.
351 – AL Open Load Cylinder B1
Yellow alarm; warning
Cause
Open circuit in cylinder B1
injector wiring. Result: Misfiring.
352 – AL Open Load Cylinder B2
Yellow alarm; warning
Cause
Open circuit in cylinder B2
injector wiring. Result: Misfiring.
353 – AL Open Load Cylinder B3
Yellow alarm; warning
Cause
Open circuit in cylinder B3
injector wiring. Result: Misfiring.
96 | Troubleshooting | MS15054/03E 2018-07
Corrective action
1. Check injector wiring, exclude disruption in solenoid valve (e.g. by
exchanging injectors).
2. Fault is rectified after each working cycle.
Corrective action
1. Check injector wiring, exclude disruption in solenoid valve (e.g. by
exchanging injectors).
2. Fault is rectified after each working cycle.
Corrective action
1. Check injector wiring, exclude disruption in solenoid valve (e.g. by
exchanging injectors).
2. Fault is rectified after each working cycle.
Corrective action
1. Check injector wiring, exclude disruption in solenoid valve (e.g. by
exchanging injectors).
2. Fault is rectified after each working cycle.
Corrective action
1. Check injector wiring, exclude disruption in solenoid valve (e.g. by
exchanging injectors).
2. Fault is rectified after each working cycle.
Corrective action
1. Check injector wiring, exclude disruption in solenoid valve (e.g. by
exchanging injectors).
2. Fault is rectified after each working cycle.