Unit Isolation

To m inim ize sound and vibration transm ission through the
building structure, and to ensure proper w eight
distribution over the m ounting surface, always install
isolation pads or spring isolators under the chiller feet.
N ot e: Isolation pads (see
chiller unless spring isolators are specified on the
sales order.
Specific isolator loading data is provided in the unit
subm ittal package. If necessary, contact your local Trane
sales office for further inform ation.
Im port ant : When determ ining placem ent of isolation
pads or spring isolators, rem em ber that the
control panel side of the unit is always
designated as the unit front.

Isolation Pads

When the unit is ready for final placem ent, position
isolation pads (457.2-m m sides) end for end under the full
length of the chiller leg. The pads m easure 228.6 m m x
457.2 m m (9 in. × 18 in.) and on som e units there m ay be
sm all gaps betw een pads. Pads are provided to cover
entire foot.
Figure 6.
Isolation pad and dimensions
9.525 m m
( 3/ 8 in.)
Rem em ber that the chiller m ust be level w ithin 1.6 m m
(1/16 in.) over its length and w idth after it is low ered onto
the isolation pads. In addition, all piping connected to the
chiller m ust be properly isolated and supported so that it
does not place any stress on the unit.

Spring Isolators

Spring isolators should be considered w henever chiller
installation is planned for an upper story location. Base
isolator placem ent is show n in
Table
3.
CVHH-SVX001A-EN
4.
Figure
6) are provided w ith each
457.2 m m
( 18 in.)
228.6 m m
( 9 in.)
Figure
7; also refer to
Figure 7.
Isolation spring placement by shell size,
evaporator and condenser length
I sola t or Con figu r a t ion 1
2
Condenser
5
Evaporat or
1
Lengt h
I sola t or Con figu r a t ion 2
2
Condenser
5
Evaporat or
1
Lengt h
Table 3.
Isolation spring placement, cm (in.)
Eva p
EV SZ
CD SZ
W idt h
W idt h Le n gt h
285.0
170.2
200L
200L
( 112.2)
( 67)
303.3
188.0
220L
220L
( 119.4)
( 74)
336.0
170.2
200L
20HL
( 132.3)
( 67)
361.0
188.0
220L
22HL
( 142.5)
( 74)
323.3
154.9
160M
20HM
( 127.3)
( 61)
285.2
170.2
200L
220L
( 112.3)
( 67)
270.3
154.9
160M
200M
( 106.4)
( 61)
264.4
100M
100M
N/ A
( 104.1)
264.4
100L
100L
N/ A
( 104.1)
277.6
130M
130M
N/ A
( 109.3)
300.2
100M
10HM
N/ A
( 118.2)
313.4
130M
13HM
N/ A
( 123.4)
Spring isolators typically ship assem bled and ready for
installation. To install and adjust the isolators properly,
follow the instructions given.
Installation: M echanical
4
Widt h
6
3
Or igin:
Right front corner of
evap r ight front foot
4
Widt h
6
Evap
Widt h
3
Or igin
Or igin
t o
t o
Ce nt e r
Ce n t e r
of
I sola t or
of Re a r
M iddle
Con fig
Pa d
Pa d
457.2
268.5
153.7
2
( 180)
( 105.7)
( 60.5)
457.2
286.8
171.5
2
( 180)
( 112.9)
( 67.5)
457.2
319.5
153.7
2
( 180)
( 125.8)
( 60.5)
457.2
345.4
171.5
2
( 180)
( 136)
( 67.5)
406.4
306.8
138.4
2
( 160)
( 120.8)
( 54.5)
457.2
268.7
153.7
2
( 180)
( 105.8)
( 60.5)
406.4
253.7
138.4
2
( 160)
( 99.9)
( 54.5)
406.4
247.9
1
N/ A
( 160)
( 97.6)
457.2
247.9
1
N/ A
( 180)
( 97.6)
406.4
261.1
1
N/ A
( 160)
( 102.8)
406.4
283.7
1
N/ A
( 160)
( 111.7)
406.4
296.9
1
N/ A
( 160)
( 116.9)
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents